Table 25 — Smoke Control Switches — PIC Controls Units
(48ZJ,ZL,ZW)*
*Units with PIC controls require installation of Controls Option Mod-
ule (PSIO2), via factory-option or field-installed accessory, for
implementation of any Smoke Control mode.
NOTE: All switches are shown in ‘‘as installed’’ (power OFF or deen-
ergized) position. In these positions, none of these modes will be
activated and normal unit operation is permitted by the base unit
controls. To initiate any mode, all switches listed under this mode in
the table must be energized, causing the contact position to change
to energized position. Switches may be manually or electrically
operated.
Table 26 — Smoke Control Switch Functions — PIC Controls Units
(48ZJ,ZL,ZW)
LEGEND *Units with PIC controls require installation of Controls Option Mod-
ule (PSIO2), via factory-option or field-installed accessory, for
implementation of any Smoke Control mode.
SMOKE
CONTROL
MODE
FIRE
SHUTDOWN
PRESSURIZATION
EVACUATION
(Modulating
Power Exhaust)
SMOKE
PURGE
SWITCHES
USED
SW-1 SW-2 SW-3 SW-4
SW-5A/B SW-5A/B
SWITCH
NUMBER
SWITCH
CONFIGURATION
VOLTAGE FUNCTION
SW-1
N.O. 24 Activate Fire Shutdown Mode
SW-2
N.O. 24 Activate Pressurization Mode
SW-3
N.O. 24 Activate Evacuation Mode
SW-4
N.O. 24 Activate Smoke Purge Mode
SW-5 A/B
A: N.O.
B: N.C.
115 Single Room Terminals to Open (HIR1)
HIR
Heat Interlock Relay
N.C.
Normally Closed
N.O.
Normally Open
14
TB2
SW-2
SW-4
SW-3
SW-1
19
22
25
28
J7
PSIO NO. 2
SIZES 030-050
PSIO NO. 2
5
TB2
SW-2
SW-4
SW-3
SW-1
19
22
25
28
J7
SIZES 055-105
TB2
SW-5A TB2
8
9
SW-5B TB2
10
TB2
8
HIR
4
6
REMOVED FROM TB2-10
TB3
SW-5A TB3
4
5
SW-5B TB3
2
TB3
4
HIR
4
6
REMOVED FROM TB3-2
Fig. 92 — PIC Units, Smoke Control Wiring