TYPICAL UNIT OPERATING PRESSURES AND TEMPERATURES
*Cooling air and water numbers can vary greatly with changes in humidity.
†Subcooling is based upon the head pressure at compressor service port Capillary Tube Expansion Device.
**Based on nominal 400 cfm per ton airflow and 70 F EAT (entering-air temperature) heating and 80/67 F EAT cooling.
ENTERING
WATER
TEMP
(F)
WATER
FLOW
GPM/
TON
COOLING* HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(°F)
Sub-
cooling†
(°F)
Water
Temp
Rise (°F)
Air
Temp**
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(°F)
Sub-
cooling
(°F)
Water
Temp
Drop
(°F DB)
Air
Temp
Rise**
(°F)
60
1.5 66-75 160-190 10-20 6-16 20-23 20-25 60-70 205-230 10-18 1- 5 12.1-14.0 23-29
2.3 65-75 145-175 15-25 8-18 12-15 20-25 63-73 210-238 10-18 1- 5 7.2- 9.0 24-30
3.0 64-74 130-160 20-30 10-20 8-12 20-25 65-75 215-242 10-18 1- 5 5.8- 6.9 25-31
70
1.5 71-82 200-230 10-20 6-16 19-22 19-24 66-72 205-230 15-25 2- 8 14.0-15.2 28-34
2.3 70-80 185-215 15-25 8-18 12-17 19-24 68-74 210-238 15-25 2- 8 9.0-10.2 30-37
3.0 69-79 175-205 20-30 10-20 7-12 19-24 70-76 215-242 15-25 2- 8 6.7- 7.9 31-38
80
1.5 75-85 230-260 10-16 5-12 19-22 18-23 68-74 205-230 20-35 2-10 14.2-15.9 32-39
2.3 74-84 215-245 13-20 7-14 12-17 18-23 70-76 210-238 20-35 2-10 9.9-11.1 33-41
3.0 72-82 200-230 15-25 8-15 7-12 18-23 72-76 215-242 20-35 2-10 6.9- 8.1 35-42
90
1.5 79-90 260-290 2- 8 1- 8 18-21 17-23
2.3 77-88 245-275 5-12 2- 9 10-14 17-23
3.0 75-87 230-260 8-16 3-10 6-11 17-23