Page view 4
5
LEGEND
NOTES:
1. A water-to-air heat pump using water or brine circulating in a common piping
loop functioning as a heat source/heat sink.
2. The temperature of the water or brine loop is usually mechanically controlled
within a temperature range of 60 F to 90 F.
3. Certified in accordance with the ARI/ISO Standard 13256-1 Certification Pro-
gram, which replaces ARI Standard-320.
4. Cooling capacities based upon 80.6 F db (dry bulb), 66.2 F wb (wet bulb) enter-
ing-air temperature.
5. Heating capacities based upon 68 F db, 59 F wb entering-air temperature.
6. All ratings based upon 208 volt operation.
50RHC,RVC
LIQUID
FLOW
(Gpm)
AIRFLOW
(Cfm)
WATER LOOP HEAT PUMP GROUND WATER HEAT PUMP GROUND LOOP HEAT PUMP
Cooling86F Heating68F Cooling59F Heating50F Cooling77F Heating32F
TC
Btuh
EER
Btuh/W
TC
Btuh
COP
TC
Btuh
EER
Btuh/W
TC
Btuh
COP
TC
Btuh
EER
Btuh/W
TC
Btuh
COP
006 1.7 220 6,400 12.5 8,300 4.2
Not Rated Not Rated
009 2.3 325 8,300 12.7 10,800 4.3
012 3.0 400 11,500 12.7 14,300 4.2
018 4.5 600 18,200 12.3 22,000 4.2
024 6.0 800 23,800 13.0 27,800 4.6
030 7.5 1000 28,000 12.2 33,500 4.4
036 9.5 1200 35,000 12.0 45,500 4.2
041 10.5 1325 37,700 12.0 47,500 4.2
042 11.0 1350 41,000 12.0 52,600 4.2
048 12.0 1600 47,100 12.2 58,200 4.4
060 15.0 2000 58,000 12.0 76,800 4.2
COP Coefficient Performance
EER Energy Efficiency Ratio
TC Total Capacity
ARI/ISO capacity ratings