Carrier 50HQ User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
11
I Determine the actual cooling and heating
loads at the desired dry bulb and wet bulb
conditions.
Assume cooling load at desired dry bulb 80 F and
wet bulb 65 F conditions are as follows:
Given:
Total Cooling (TC). . . . . . . . . . . . . . .65,500 Btuh
Sensible Cooling (SC) . . . . . . . . . . . .54,700 Btuh
Entering-Air Temperature db . . . . . . . . . . . . .80 F
Entering-Air Temperature wb . . . . . . . . . . . . .65 F
II Determine the following design parameters.
Entering water temperature, water flow rate (gpm),
airflow (cfm), water flow pressure drop and design
wet and dry bulb temperatures. Airflow cfm should
be between 300 and 450 cfm per ton. Unit water
pressure drop should be kept as close as possible
to each other to make water balancing easier. Enter
the appropriate Performance Data tables and
find the proper indicated water flow and water
temperature.
For example:
Entering Water Temp (Cooling) . . . . . . . . . . .90 F
Entering Water Temp (Heating) . . . . . . . . . . .60 F
Water Flow . . . . . . . . . . . . . . . . . . . . 15.0 GPM
Airflow Cfm . . . . . . . . . 2100 Cfm (350 Cfm/Ton)
III Select a unit based on total cooling and total
sensible cooling conditions. Unit selected
should be closest to but not larger than the
actual cooling load.
Enter tables at the design water flow and water
temperature. Read the total and sensible cooling
capacities.
NOTE: Interpolation is permissible, extrapolation is
not.
Example equipment selection for cooling:
Enter the 50HQP072 Performance Table at design
water flow and water temperature. Read Total
Cooling, Sensible Cooling and Heat of Rejection
capacities:
Total Cooling . . . . . . . . . . . . . . . . . .67,500 Btuh
Sensible Cooling . . . . . . . . . . . . . . . .52,300 Btuh
Heat of Rejection . . . . . . . . . . . . . . .87,900 Btuh
Airflow Cfm . . . . . . . . . . . . . . . . . . . . 2400 Cfm
NOTE: It is normal for water source heat pumps to
be selected on cooling capacity only since the heat-
ing output is usually greater than the cooling capac-
ity.
IV Determine the correction factors associated
with the variable factors of dry bulb and wet
bulb using the Corrections Factor tables
found in this book.
Using the following formulas to determine the cor-
rection factors of dry bulb and wet bulb:
a) Corrected Total Cooling = tabulated total cooling
x wet bulb correction x airflow correction.
b) Corrected Sensible Cooling = tabulated sensible
cooling x wet/dry bulb correction x airflow
correction.
V Determine entering air and airflow correction
using the Corrections Factor tables found in
this book.
The nominal airflow for the 50HQP072 is 2400
cfm. The design parameter is 2100 cfm.
2100/2400 = 88% of nominal airflow. Use the
88% row in the Airflow Correction table.
The nominal EAT (wb) is 67 F. The design parame-
ter is 65 F. Use the 65 F correction factor row from
the Entering Air Correction Factors table. Use
design temperature 80 F (db) column for sensible
cooling correction.
Using the following formulas to determine the cor-
rection factors of entering air and airflow correction:
Compare the corrected capacities to the load
requirements established in Step I. If the capacities
are within 10% of the load requirements, the equip-
ment is acceptable. It is better to undersize than
oversize as undersizing improves humidity control,
reduces sound levels and extends the life of the
equipment.
VI Determine the correction factor associated
with antifreeze in system loop.
If heating EWT is 50 F or below, antifreeze may
need to be used. Calculate leaving water tempera-
ture per performance data selection notes (opera-
tion is shaded areas). If antifreeze is required, use
Anti-Freeze Correction table for correcting total and
sensible capacities.
If the EWT for heating is 40 F, then the system
requires antifreeze. If a solution of 15% propylene
glycol is required, then:
Corrected Total Cooling =64,365 x 0.986
Corrected Total Cooling =63,464
Corrected Sensible Cooling =53,139 x 0.986
Corrected Sensible Cooling =52,395
VII Water temperature rise calculation and
assessment.
Calculate the water temperature rise and assess the
selection using the following calculation:
Table Ent Air Airflow Corrected
Corrected Total
Cooling
= 67,500 x 0.977 x 0.976 = 64,365
Corrected Sensi-
ble Cooling
= 52,300 x 1.089 x 0.933 = 53,139
Corrected Heat
of Rejection
= 87,900 x 0.998 x 0.976 = 85,619
Actual Temperature
Rise =
Correction of
Heat of Rejection
GPM x 500
Selection procedure
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 33 34

Comments to this Manuals

No comments