Carrier 50HQ User Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
14
50HQP072
2400 CFM NOMINAL AIRFLOW
LEGEND NOTES:
1. Interpolation is permissible, extrapolation is not.
2. All entering air conditions are 80 F db (dry bulb) and 67 F wb (wet bulb) in
cooling and 70 F db in heating.
3. AHRI/ISO certified conditions are 80.6 F db and 66.2 F wb in cooling and
68 F db in heating.
4. Table does not reflect fan or pump power corrections for AHRI/ISO condi-
tions.
5. All performance data is based upon the lower voltage of dual voltage rated
units.
6. Performance stated is at the rated power supply. Performance may vary as
the power supply varies from the rated voltage.
7. Operation below 60 F EWT requires optional insulated water circuit.
8. Operation below 40 F EWT is based upon 15% methanol antifreeze solu-
tion.
9. See Correction Factor tables for operating conditions other than those listed
above.
10. Performance capacities shown in MBtuh.
OPERATION IN SHADED AREAS
For operation in the shaded area when water is used in lieu of an anti-freeze solu-
tion, the LWT (Leaving Water Temperature) must be calculated. Flow must be
maintained to a level such that the LWT is maintained above 42 F [5.6 C] when
operating in the standard range. This is due to the potential of the refrigerant tem-
perature being as low as 32 F [0° C] with 40 F [4.4 C] LWT, which may lead to a
nuisance cutout due to the activation of the Low Temperature Protection.
Example:
At 50 F EWT (Entering Water Temperature) and 15 gpm, a 50HQP072 unit has a
THA of 57,800 Btuh. To calculate LWT, rearrange the formula for THA as follows:
THA = TD x GPM x 500, where THA = Total Heat of Absoption (Btuh); TD = tem-
perature difference (EWT - LWT) and GPM = U.S. Gallons per Minute.
TD = THA / (GPM x 500)
TD = 57,800 / (15 x 500)
TD = 8 F
LWT = EWT - TD
LWT = 50 - 8 = 42 F
In this example, a higher flow rate will be required for EWTs at or below 50 F with-
out antifreeze.
EWT (F) GPM
PRESSURE DROP COOLING CAPACITY HEATING CAPACITY
PSIG
FT
WG
TC TSC kW THR EER HC kW THA LAT COP
20 20 6.8 15.8 Operation Not Recommended
49.5 5.0 32.5 87.1 2.9
30
10 1.2 2.7 82.3 56.8 3.6 94.5 23.0
54.7 5.0 37.5 89.0 3.2
15 3.3 7.7 81.1 55.8 3.4 92.8 23.6 56.8 5.1 39.6 89.9 3.3
20 6.2 14.3 80.2 55.1 3.4 91.7 23.8
58.0 5.1 40.7 90.3 3.4
40
10 1.0 2.2 82.4 57.4 3.9 95.6 21.2
63.2 5.1 45.6 92.3 3.6
15 3.0 7.0 82.6 57.1 3.7 95.1 22.4 66.1 5.2 48.4 93.4 3.7
20 5.6 13.0 82.4 56.8 3.6 94.6 22.9
67.7 5.2 50.0 94.1 3.8
50
10 0.9 2.0 80.7 57.2 4.2 95.1 19.0
72.3 5.3 54.4 95.8 4.0
15 2.8 6.5 81.9 57.4 4.0 95.6 20.5 76.0 5.3 57.8 97.2 4.2
20 5.3 12.2 82.3 57.4 3.9 95.6 21.1
78.0 5.4 59.7 98.0 4.3
60
10 0.5 1.2 77.7 56.3 4.7 93.6 16.7 81.8 5.4 63.3 99.5 4.4
15 2.2 5.1 79.7 56.9 4.4 94.7 18.2 86.0 5.5 67.2 101.1 4.6
20 4.4 10.1 80.6 57.2 4.3 95.1 18.9 88.3 5.5 69.4 102.0 4.7
70
10 0.5 1.1 73.9 54.9 5.2 91.4 14.3 91.1 5.6 72.0 103.1 4.8
15 2.1 4.8 76.3 55.8 4.8 92.8 15.8 95.6 5.7 76.3 104.8 4.9
20 4.2 9.6 77.5 56.2 4.69 93.5 16.5 98.0 5.7 78.5 105.7 5.0
80
10 0.4 0.9 69.4 53.1 5.71 88.9 12.2 99.8 5.880.2 106.4 5.1
15 1.9 4.5 72.2 54.2 5.37 90.5 13.4 104.4 5.9 84.4 108.2 5.2
20 3.9 9.1 73.5 54.7 5.20 91.2 14.1 106.7 5.9 86.5 109.1 5.3
85
10 0.4 0.8 67.1 52.1 6.03 87.7 11.2 103.7 5.883.8 107.9 5.2
15 1.9 4.4 69.8 53.3 5.66 89.2 12.4 108.0 5.9 87.8 109.6 5.3
20 3.9 8.9 71.2 53.8 5.49 8 9.9 13.0 110.1 6.0 89.7 110.4 5.4
90
10 0.3 0.8 64.8 51.2 6.35 86.4 10.2 107.6 5.9 87.4 109.4 5.3
15 1.8 4.3 67.5 52.3 5.96
87.9 11.3 111.7 6.0 91.1 111.0 5.4
20 3.88.8 68.9 52.9 5.7888.6 11.9 113.5 6.0 92.8 111.7 5.5
100
10 0.3 0.7 60.1 49.2 7.06 84.2 8.5
Operation Not Recommended
15 1.8 4.1 62.7 50.3 6.64 85.4 9.4
20 3.7 8.5 64.1 50.9 6.44 86.1 10.0
110
10 0.2 0.6 55.8 47.5 7.87 82.7 7.1
15 1.7 3.9 58.1 48.4 7.41 83.4 7.8
20 3.6 8.3 59.4 48.9 7.19 83.9 8.3
120
10 0.2 0.5 52.2 46.3 8.7882.2 5.9
15 1.6 3.7 54.1 46.9 8.27 82.3 6.5
20 3.5 8.0 55.1 47.3 8.02 82.5 6.9
See below
COP Coefficient of Performance
EER Energy Efficiency Ratio
EWT Entering Water Temperature
GPM Gallons Per Minute
HC Heating Capacity
kW Total Power (Kilowatts)
LAT Leaving Air Temperature
MBtuh Btuh in Thousands
TC Total Capacity (MBtuh)
THA Total Heat of Absorption (MBtuh)
THR Total Heat of Rejection (MBtuh)
TSC Total Sensible Capacity (MBtuh)
Performance data (cont)
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 33 34

Comments to this Manuals

No comments