50HQP072-120 UNITS
LEGEND NOTES:
1. Cooling capacities based upon 80.6 F db, 66.2 F wb entering air
temperature.
2. Heating capacities based upon 68 F db, 59 F wb entering air
temperature.
3. All ratings based upon operation at lower voltage of dual voltage
rated models.
4. All 50HQP072 ratings are at 2400 cfm (1133 l/s) with 20 gpm
(1.26 l/s). Sheave setting for AHRI is 2.5 turns open.
5. All 50HQP096 ratings are at 3200 cfm (1510 l/s) with 24 gpm
(1.51 l/s). Sheave setting for AHRI is 3.0 turns open.
6. All 50HQP120 ratings are at 4000 cfm (1888 l/s) with 30 gpm
(1.89 l/s). Sheave setting for AHRI is 3.0 turns open.
UNIT GPM CFM
WATER LOOP HEAT PUMP GROUND WATER HEAT PUMP GROUND LOOP HEAT PUMP
Cooling 86FHeating 68F Cooling 59F Heating 50F Cooling 77F Heating 32F
Total
Capacity
(Btuh)
EER
(Btuh/W)
Total
Capacity
(Btuh)
COP
Total
Capacity
(Btuh)
EER
(Btuh/W)
Total
Capacity
(Btuh)
COP
Total
Capacity
(Btuh)
EER
(Btuh/W)
Total
Capacity
(Btuh)
COP
50HQP072 20.0 2400 69,000 13.3 92,500 5.0 78,500 19.7 75,500 4.4 71,000 14.6 58,000 3.5
50HQP096 24.0 3200 95,600 13.7 123,000 5.0 104,500 20.0 101,000 4.4 98,000 15.2 77,000 3.6
50HQP120 30.0 4000 119,000 13.3 160,000 4.6 134,000 19.3 132,500 4.0 122,500 14.5 103,000 3.3
COP Coefficient of Performance
db —Dry Bulb
EER Energy Efficiency Ratio
wb —Wet Bulb
AHRI/ISO capacity ratings