Carrier 50HQ User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
3
compressor section from 3 sides.
Additional panels are provided to
access the blower and control box sec-
tions.
The blower housing assembly can be
serviced without disconnecting duct-
work from the dedicated blower access
panel. Blower units are provided with
permanently lubricated bearings for
worry-free performance.
Electrical disconnection of the
blower motor and control box is easily
accomplished from quick disconnects
on each component.
Easy removal of the control box
from the unit provides access to all
refrigeration components.
The refrigeration circuit is easily
tested and serviced through the use of
high and low pressure ports integral to
the refrigeration circuit.
Maximum control flexibility
Aquazone water source heat pumps
provide reliable control operation using
a standard microprocessor board with
flexible alternatives for many direct dig-
ital control (DDC) applications includ-
ing the Carrier Comfort Network®
(CCN) and open protocol systems.
Carrier’s Aquazone standard unit
solid-state control system, the Com-
plete C, provides control of the unit
compressor, reversing valve, fan, safety
features, and troubleshooting fault indi-
cation features. The Complete C con-
trol system is one of the most user
friendly, low cost, and advanced con-
trol boards found in the WSHP indus-
try. Many features are field selectable
to provide the ultimate in field installa-
tion flexibility. The overall features of
this standard control system include:
75-va transformer assists in accom-
modating accessory loads.
Anti-short cycle timer provides a
minimum off time to prevent the unit
from short cycling. The 5-minute timer
energizes when the compressor is
deenergized, resulting in a 5-minute
delay before the unit can be restarted.
Random start relay ensures a ran-
dom delay in energizing each different
WSHP unit. This option minimizes
peak electrical demand during start-up
from different operating modes or after
building power outages.
High and low pressure refrigerant
protection safeguards against unreli-
able unit operation and prevents refrig-
erant from leaking.
Condensate overflow sensor,
mounted to the drain pan, recognizes
thirty continuous seconds of conden-
sate pan overflow as a fault. When
condensate pan liquid reaches an unac-
ceptable level, unit is automatically
deactivated and placed in a lockout
condition.
High and low voltage protection
safe guards against excessive or low
voltage conditions.
Automatic intelligent reset auto-
matically restarts unit 5 minutes after
shutdown if the fault has cleared.
Should a fault occur 3 times sequen-
tially, lockout will occur.
Accessory output (24-v) is provided
to cycle a motorized water valve or
damper actuator with compressor in
applications such as variable speed
pumping arrangements.
Performance Monitor (PM) feature
monitors water temperatures to warn
when the heat pump is operating inef-
ficiently or beyond typical operating
range. Field selectable switch initiates a
warning code on the unit display.
Water coil freeze protection
(selectable for water or anti-
freeze) field selectable switch for water
and water/glycol solution systems initi-
ates a fault when temperatures exceed
the selected limit for 30 continuous
seconds.
Air coil freeze protection (check
filter operation) field selectable
switch for assessing excessive filter
pressure drop initiates a fault when
temperatures exceed the selected limit
for 30 continuous seconds.
Alarm relay setting is a selectable
24-v or pilot duty dry contact for pro-
viding activation of a remote alarm.
Electric heat option output pro-
vided on the controller for operating
two stages of emergency electric heat.
Service test mode with diagnostic
LED (Light-emitting diode) allows
service personnel to check the opera-
tion of the WSHP and control system
efficiently. Upon entering Test mode,
time delays are sped up, and the Status
LED will flash a code to indicate the
last fault experienced for easy diagno-
sis. Based on the fault code flashed by
the status LED, system diagnostics are
assisted through the use of Carrier pro-
vided troubleshooting tables for easy
reference to typical problems.
LED visual output indicates high
pressure, low pressure, low voltage,
high voltage, air/water freeze protec-
tion, condensate overflow, and control
status on an LED panel.
Open protocol for diverse control
(LON controller) option is ideal
when building automation requires
interoperability across diverse control
platforms. This LONMark* compliant
offering can operate as standalone or
as a part of Local Operating Network
(LON) via the LonWorks* FTT-10
Free
Topology communication network.
Fac-
tory completed, pre-engineered appli-
cations specific to Aquazone water
source heat pumps and digital wall sen-
sors communicating over Sensor Link
(S-Link) communication protocol com-
pletes a system of networked control.
Carrier’s PremierLink™ con-
troller adds reliability, effi-
ciency, and simplification
The PremierLink direct digital control-
ler can be ordered as a factory-installed
option. Designed and manufactured
exclusively by Carrier, the controller
can be used to actively monitor and
control all modes of operation as well
as monitor the following diagnostics
and features: unit number, zone tem-
perature, zone set point, zone humidity
set point, discharge-air temperatures,
fan status, stages of heating, stages of
cooling, outdoor-air temperature,
leaving-air temperature, leaving water
temperature, alarm status, and alarm
lockout condition.
This controller has a 38.4K baud
communications capability and is
compatible with ComfortLink™ con-
trols, CCN and ComfortVIEW™ soft-
ware. The scrolling marquee and Navi-
gator™ display are optional tools that
can be used for programming and
monitoring the unit for optimal perfor-
mance. The addition of an accessory
CO
2
sensor in the conditioned space
provides ASHRAE 62-99 compliance
and demand controlled ventilation
(DCV). A DCV control strategy is espe-
cially beneficial for a water source heat
pump system to minimize the energy
utilized to condition ventilation air.
The DCV approach enhances the en-
ergy efficient performance of the
Aquazone™ units.
The PremierLink peer-to-peer, Internet
ready communicating control is
designed specifically for constant vol-
ume (CV) and variable volume and vari-
able temperature (VVT®) applications.
This comprehensive controls system
allows water source heat pumps to be
linked together to create a fully func-
tional HVAC (heating, ventilation, and
air conditioning) automation system.
* Registered trademark of Echelon Corporation.
Page view 2
1 2 3 4 5 6 7 8 ... 33 34

Comments to this Manuals