1--14
62--10828
Change 06/09
1.6.2 Compressor Data
Model (Unit)
05K 012 (550/650/750) 05K 024 (850) 05G37 (950)
Displacement 12.2 in
3(
200 cc) 24.4 in
3
(400 cc) 37 in
3
(600 cc)
No. Cylinders 2 4 6
No. Unloaders 0 1 1
Weight 84 lbs (38 kg) 108 lbs (49 kg) 137lbs (62 kg)
Oil Charge 4.0 pints (1.9 L) 5.5 pts (2.6 L) 6.75 pts (3.2)
APPROVED COMPRESSOR OIL
Refrigerant 05G/05K
R-404A
Mobile Arctic EAL 68
Castrol Icematic SW-68C
a. High Pressure Switches
HP1
Opens on a pressure rise at: 465 +/-- 10 psig (32.7
+/-- 0.7 kg/cm@)
Closes on a pressure fall at: 350 +/-- 10 psig (24.6 +/--
0.7 kg/cm@)
HP2 850 Only
Closes on a pressure rise at: 440 +/-- 10 psig (29.9
+/-- 0.7 kg/cm@)
Opens on a pressure fall at: 367 +/-- 12 psig (25 +/--
0.8 kg/cm@)
b. Compressor Discharge Temperature Sensor
(CDT)
This is a thermistor type sensor located (when installed)
on the compressor discharge cover.
Unit shuts down:
SIf ambient is less than 120°F(50°C) AND
Temperature exceeds 310°F (154°C) for 3 min
SIf ambient is greater than 120°F(50°C) AND
Temperature exceeds 340°F (171°C) for 3 min
SImmediately shuts down in all ambients
If temperature exceeds 350°F (177°C)
1.6.3 Refrigeration System Data
a. Defrost Timer
1-1/2, 3, 6, or 12 hours
b. Defrost Thermostat
Opens at: 47_ +/ -- 5_F(8_ +/-- 3_C)
Closes at: 37_ +/-- 5_F(3_ +/-- 3_C)
c. Defrost Air Switch Setting
550/650/750; Initiates at: 1.00 +/-- .07 inch
(25.4 ¦ 1.8 mm) wg
850/950; Initiates at: 0.70 +/-- .07 inch
(17.8 +/-- 1.8 mm) wg
d. Refrigerant Charge
RefertoTable1-1
e. Compressor Pressure Regulating Valve (CPR)
MODEL
CPR Setting CPR Setting
psig Bars
SUPRA 550 34 +/-- 1 2.3 +/-- 0.07
SUPRA 650 28 +/-- 1 1.91 +/-- 0.07
SUPRA 750 32 +/-- 1 2.18 +/-- 0.07
SUPRA 850/950 29 +/-- 1 1.97 +/-- 0.07
f. Thermostatic Expansion Valve Superheat
Setting at 0_F (--17.8_ C) box temperature: 8-10_F
(--13.3 to --12.2_C)