2.4.10 Functional Parameters
NOTE
If configuration CNF11 is “ON” functional pa-
rameters are locked out and the ability to
change functional parameters from keypad is
disabled.
The Function Parameters control selected operating
features of the unit. These parameters can be displayed
by pressing the FUNCTION CHANGE key. When multi-
ple choices are available, the display will show the func-
tion description on the left side with the corresponding
function choice on the right side. The list can be scrolled
through by pressing the FUNCTION CHANGE key or by
using the ARROW keys. With each FUNCTION
CHANGE key push, the list is advanced one. If the
FUNCTION CHANGE key is pressed and held for one
second, the list will scroll at a rate of one item every 0.5
seconds. Once the end of the list is reached the list will
scroll back to the first entry.
With a function parameter displayed, the data choice
can be changed by pressing ENTER then pressing ei-
ther the up or down ARROW keys. The displayed choice
will then flash to indicate that the choice has not been
entered. Depress the ENTER key to activate the new
choice. The display will stop flashing to indicate that the
choice has been entered.
If the new choice is not entered in 5 seconds, the display
will revert back to the last entered choice. All function
parameters are retained in memory. Descriptions of the
function parameters and operator choices are provided
in the following paragraphs. A function parameter listing
is also provided in Table 2-1.
Defrost Interval
The English display for Defrost Interval is DEFR” the
code display is “FN0.” The choices are displayed with
one decimal place and then the capital letter H for hours
(i.e., DEFR 12.0H). The defrost choices are 1.5, 3, 6 or
12 hours.
Speed Control
The Speed Control parameter overrides the normal mi-
croprocessor speed control solenoid operation. Param-
eter English displays are “CITY SPD” or “HIGH SPD.”
The code displays are “FN1 ON” or “FN1 OFF.” With
“CITY SPD” or “FN1 ON” displayed the unit is locked
into low speed. With “HIGH SPD” or “FN1 OFF” dis-
played, speed is under normal microprocessor control.
Minimum Off-Time
The auto start mode Minimum Off-Time parameter En-
glish display is “OFF T” the code display is “FN2. The
choice for the off-time is displayed with two digits and
then the capital letter M for minutes (i.e. OFF T 20M or
FN2 20M). The off-time choices are 10, 20, 30, 45 or 90
minutes.
Minimum On-Time
The auto start mode Minimum On-Time parameter En-
glish display is “ON T.” The code display is “FN3. The
choice for the on-time is displayed with two digits and
then the capital letter M for minutes (i.e. ON T4 M).The
on-time choices are 1 or 4 minutes.
Controlling Probe
The Controlling Probe parameter English displays are
“REM PROBE” or “SUP PROBE. The code displays
are “FN4 A” or “FN4 B.” With “REM PROBE” or “FN4 A”
displayed, the microprocessor is set for operation with a
single probe sensing return air temperature. With “SUP
PROBE” or FN4 B” displayed, the microprocessor is
set for dual probe (supply air or return air) control.
Standard Units Select
The Standard Unit Select parameter allows selection of
English or metric data display. The English display is DE-
GREES F or C. The code display is FN5. The choices
are_C and _F. This parameter will also convert pressure
readings to psig or bars.
Maximum Off Time
The auto start mode Maximum Off Time English display
is “TIME START” or “TEMP START” the code display is
“FN6 ON” or “FN6 OFF.” With “TIME START” or “FN6
ON” displayed the engine will be started 30 minutes
after shutdown. With TEMP START” or “FN6 OFF”
displayed the engine will be under normal microproces-
sor temperature control.
Diesel Backup Feature:
If the unit is in standby mode and AC power is lost for five
minutes or more, the diesel engine will start and run until
AC power is restored and applied for five minutes. The
ROAD icon will blink once every second while the PLUG
icon will stay on constantly to indicate that this feature is
active.
When the five minute shutdown timer expires and AC
power is present, the unit will shut down the diesel en-
gine and restart the standby motor. If AC power is NOT
present, the diesel engine will operate.
If the unit is set to TEMP START” the standby diesel
back up feature will be turned off and the unit will operate
in normal standby mode.
MOP STD - Future Expansion
Used to add or subtract 5psig (0.34 Bar) to unloader
equat
ions. English display is MOP STD.” The code
displayis“FN7
Compartment 2 Setpoint - N/A
English display is “2SET. The code display is “FN8”
Compartment 3 Setpoint - N/A
English display is “3SET. The code display is “FN9”
Auto/Manual Start Operation
The English displays for Auto/Manual Start Operation
are “AUTO OP” and “MAN OP.” The code displays are
“FN10 ON” and “FN10 OFF. With AUTO OP” or “FN10
ON” displayed the unit will be in the Auto Start/Stop
Operation mode. With “MAN OP or “FN10 OFF dis-
played the unit will be in the Manual Start mode.
To start the unit in manual start mode, the Auto Start/-
Stop - Continuous Run selection must be in “continuous
run” mode.