2--10
62--10828
Low Oil Pressure Alarm
The English display for the Low Oil Pressure alarm is
“ENG OIL.” The code display is “AL0.” This alarm is
generated if the microprocessor senses low oil pressure
any time after a short delay allowed at startup. When
this alarm is generated, the fault light will illuminate and
the engine will shut down.
High Coolant Temperature Alarm
The English display for the High Coolant Temperature
alarm is “ENG HOT.” The code display is “AL1.” This
alarm is generated if the microprocessor senses coolant
temperature above 230_F(110_C). When this alarm is
generated, the fault light will illuminate and the engine
will shut down.
High Pressure Alarm
The English display for the High Pressure alarm is “HI
PRESS.” The code display is “AL2.” This alarm is gener-
ated if the high pressure switch opens. When this alarm
is generated, the fault light will illuminate and the engine
will shut down.
Start Failure Alarm
The English display for the Start Failure alarm is
“STARTFAIL.” The code display is “AL3.” This alarm is
generated if the start sequence has completed and the
engine has failed to start. When this alarm is generated,
the fault light will illuminate.
If function parameter MAN OP (FN10 OFF) is selected
the start failure alarm will be generated if the engine is
not started in five minutes.
Low Battery Voltage Alarm
The English display for the Low Battery Voltage alarm is
“LOW BATT.” The code display is “AL4.” This alarm is
generated if the battery voltage falls below 10 VDC.
When this alarm is generated, the fault light will illumi-
nate.
High Battery Voltage Alarm
The English display for the High Battery Voltage alarm is
“HIBATT.” The code display is “AL5.” This alarm is gen-
erated if the battery voltage rises to 17 VDC. When this
alarm is generated, the fault light will illuminate and the
engine will shut down.
Defrost Override Alarm
The English display for the Defrost Override alarm is
“DEFR FAIL.” The code display is “AL6.” This alarm is
generated if the defrost has been terminated by the 45
minute timer. The fault light will not be illuminated by this
alarm.
Alternator Auxiliary Alarm
The English display for the Alternator Auxiliary alarm is
“ALT AUX.” The code display is “AL7.” This alarm is
generated if the alternator auxiliary signal is not present
with the engine running. When this alarm is generated,
the fault light will illuminate.
Starter Motor Alarm
The English display for the Starter Motor alarm is
“STARTER.” The code display is “AL8.”This alarm is
generated if the starter motor input signal is not present
with starter solenoid energized. When this alarm is gen-
erated, the fault light will illuminate.
Return Air Sensor Alarm
The English display for the Return Air Sensor alarm is
“RA SENSOR.” The code display is “AL9.” This alarm is
generated if the return air sensor is open or shorted.
If the microprocessor is set to allow operation on a sec-
ond sensor, it will switch control to that sensor. If the unit
is not fitted with a second sensor or if the microproces-
sor is not set to allow control on the second sensor, one
of two actions will be taken.
1. If the unit is operating in the perishable range, the
unit will shut down.
2. If the unit is operating in the frozen range, the unit will
switch to low speed cool.
When this alarm is generated, the fault light will illumi-
nate.
Supply Air Sensor Alarm
The English display for the Supply Air Sensor alarm is
“SA SENSOR.” The code display is “AL10.” This alarm
is generated if the supply air sensor is open or shorted.
This alarm will be disabled if the REM PROBE (FN4 A) is
selected in the controlling probe functional parameter.
The fault light will not be illuminated by this alarm.
Coolant Temperature Sensor Alarm
The English display for the Coolant Temperature Sen-
sor alarm is “WT SENSOR.” The code display is “AL11.”
This alarm is generated if the coolant temperature sen-
sor is open or shorted. The fault light will not be illumi-
nated by this alarm.
Compressor Discharge Temperature Alarm
The English display for the Compressor Discharge Tem-
perature alarm is “HIGH CDT.” The code display is
“AL12.” This alarm is generated if the microprocessor
senses discharge temperature above 310_F (155_C)
f
or 3 minutes. When this alarm is generated, the fault
light will illuminate.
If the discharge temperature exceeds 350_ F (177_C),
the fault light will illuminate and the engine will be shut
down immediately.
Compressor Discharge Temperature Sensor Alarm
The English display for the Compressor Discharge Tem-
perature Sensor alarm is “CD SENSOR.” The code dis-
play is “AL13.” This alarm is generated if the sensor is
open or shorted. The fault light will not be illuminated by
this alarm.
Standby Motor Overload Alarm
The English display for the Standby Motor Overload
alarm is “SBY MOTOR.” The code display is “AL14.”
This alarm is generated if the MOL is open and the
diesel/electric relay is energized (indicating standby
mode).
Fuse Alarm
The English display for the Fuse alarm is “FUSE BAD .”
The code display is “AL15.” This alarm is generated
when the FUSE input is sensed low. When this alarm is
generated, the fault light will illuminate.