Table 1D -- Physical Data -- 38ARQ008,012 and 38AQS016 Units -- 50 Hz Sl
UNIT 38ARQ008 38ARQ012 38AOS016
NOMINAL CAPACITY (kW) 22.1 29.2 43.9
OPERATING WEIGHTS (kg)
Aluminum-Fin Coils (standard) 210 230 365
Copper-Fin Coils (optional) 256 275 430
REFRIGERANT* R-22
Operating Charge, Typical (kg)t 9 I 10 17
Shipping Charge (kg) 4.1 I 4.1 1.3
Scroll Semi-hermetic
reciprocating
1...ZR 94 / 1...ZR125 1...06DF537tt
2.7- t 3.3 3.8
NA 6
58 I 58 29
2...15 2...15
560 660
.19 .37
2740 3500
2 1
2.7 2.7
2...670 3...590
15.5 18.2
COMPRESSOR
Qty._Model
Oil Charge (L)
No. Cylinders
Speed (r/s)
OUTDOOR FANS
Qty...r/s
Diameter (ram)
Nominal kW
Nominal Airflow (L/s total)
OUTDOOR COILS (Qty)
Face Area (sq m total)
Rows...Fins/m
Storage Capacity (kg)**
CONTROLS
Pressurestat Settings (kPag)
High Pressure
Open
Close
Low Pressure
Open
Close
PIPING CONNECTIONS (in. ODM)
Vapor
Liquid
2950_+ 70 I 2725_+135
2200 _+138 I 2035 _+135
48 _+20 I 48 _+20
150 _+35 I 150 _+35
11/8 13/8 I 1s/8
1/2 1/2 I 5/8
*Unit is factory supplied with holding charge only.
tTypical operating charge with 7.6 m of interconnecting pipe.
**Storage capacity of condenser coil with 80% full of liquid at 36 C.
1-tEquipped with an electric solenoid unloader, capacity steps 100% and 67%.