COMPRESSOR _ REVERSING VALVE
?M ULAT_'_O R _ VAPOR-_LINE
CK VALVE B
1]
CK VALVE A
CK VALVE C
f
II
FILTER
DRIER
d&
FIXED ORIFICE
METERING DEVICE
LIQUID LINE
Fig. 21 -- 38ARQ008, 012 Heating Mode (Size 008 Shown)
TO
INDOOR
UNIT
BALL
VALVE
?
FROM
[_ INDOOR
BALL UNIT
VALVE
38AQS016 Cooling Mode Operation
(See Fig. 22)
I. High pressure, high temperature lefrigemnt vapor froln
the compressor flows through the reversing valve and is
directed to the outdoor coil vapor headel:
2. At the outdoor coil vapor headel: the high pressure, high
temperature refrigerant vapor flows up to check valve
"A" that blocks the flow. All the refrigerant is then
directed to flow into the coil circuits.
Subcooled refrigerant liquid leaves the coil circuits
entering the portion of the vapor header which is above
check valve "A". Check valve "C" is closed, therefore,
the liquid refrigerant passes through check valve "B,"
which is open, and enters the liquid line and goes to the
indoor coil.
4. The liquid refrigerant is expanded and evaporated in the
indoor coil resulting in low pressure vapor This low
plessure vapor returns to the outdoor unit through the
system vapor line, reversing valve, and accumulator.
reentering the compressor at the suction connection.
38AQ8016 Heating Mode Operation
(See Fig. 23)
I. High pressure, high temperature lefrigemnt vapor froln
the compressor flows through the reversing valve and
is directed through the system vapor line to the indoor
coil. Refrigerant is condensed and subcooled in the
indoor coil and returns to the outdoor unit through the
system liquid line.
2. Check valve "B" blocks the flow of liquid and the refiig-
erant is then directed to flow through check wtlve "C"
(which is open), through the filter drier, and into the
liquid header assembly.
3. The liquid refrigerant is expanded as it passes through the
capillary tubes into outdoor coil circuits. The refrigerant
evaporates as it passes through the coil circuits resulting
in low plessure vapol:
4. The low pressme vapor leaves the coil circuits and enters
the vapor headek check valve "A" is open, and returns to
the compressor through the vapor line, leversing v;dve,
and accumulator. _eentering the compressor at the suction
connection.
Crankcase Heater--The crankcase heater prevents
refrigerant migration and compressor oil dilution during
shutdown when compressor is not operating.
Close both compressor service valves when crankcase
heater is deenergized for more than 6 houL's.
Outdoor Unit Fans--Each fan is supported by a
formed-wire mount bolted to the fan deck and covered with a
wire guard. On the 38AQS016, the exposed end of the motor
shaft is covered with a rubber boot. In case a fan motor must be
repaired or leplaced, be sure the rubber boot is put back on
when the fan is reinstalled and be sure the fan guard is in place
before stmting the unit.
Lubrication--Fan motors have permanently sealed
bemings. No further lubrication is required.
24