Carrier 38AQ Specifications Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Defrostis achievedby reversalfiomheatingto cooling
cycleanddeenergizationof outdoor-fanmotol.'s,allowinghot
refrigerantgastodefrostoutdoorcoil.Defrostisachievedwith
a timersetto initiatedefrostevery30,50,or 90minutes
(factorysetat30minutes).
Defrostisinitiatedwhenrefrigeranttemperatureleavingthe
outdoorcoilismeasuredbelow27F(2.8C),(typicallywhen
theoutdoorambienttemperatureis below45F [7.2C] as
sensedbythedefiostthermostat[DFTI).
Defrostis terminatedwhen:Therefrigeranttemperature
risesto65F(18.3C)(80F[26.7C]for38AQS016)attheDFT
locationontheliquidline;ortherefrigerantpressurerisesto
280psig(1931kPag)attheHPS2locationontheliquidline;or
thedefiosttimercompletesthe10-minntecycle.
Duplex Units
DUPLEX 38ARQ012 UNITS WITH 40RMQ024 (See
Fig. 12)
Cooling -- When the thermostat is set for cooling, and the
space temperature comes within 2° F (1 o C) of the cooling set
point, the thermostat completes the circuit from R to O and the
reversing valves in both units are energized. If the space tem-
perature continues to rise, the circuit from R to YI is complet-
ed. If the time delays and safeties are satisfied, the compressor
contactor closes, starting the compressor and outdoor-fan
motors of Heat Pump A. At the same time the circuit is
completed from R to G. starting the indoor-fan motor. If the
space temperature continues to rise, the circuit is completed
from R to Y2 and the Cooling mode is initiated in Heat Pump
B in a similar mannec
When the thermostat is satisfied, the contacts open, deener-
gizing first the Heat Pump B and then Heat Pump A.
Heating -- When the thermostat c_dls for heating, the circuit
fiom R to YI is completed. If the time delays and safeties are
satisfied, the compressor contactor closes, sttuting the com-
pressor and outdoor-fan motors of Heat Pump A and Heat
Pump B. At the same time the circuit is completed from R to G.
st_uting the indoor-fan motol: If the second stage of heating is
required, the circuit from R to W2 will be completed and the
electric resistance heaters will be energized.
When the thermostat is satisfied, the contacts open, deener-
gizing Heat Pump A and Heat Pump B.
DUPLEX 38AQS016 AND 38ARQ012 UNITS WITH
40RMQ028 (See Fig. 13)
Cooling -- When the thermostat calls for cooling, the circuit
from R to YI is completed. If the time delays and safeties are
satisfied, the compressor contactor closes, sttuting the com-
pressor and outdoor-fan motors of Heat Pump A (38AQS016).
At the same time the circuit is completed form R to G. stmling
the indoor-fan motol: If the space temperature continues to rise,
the circuit is completed from R to Y2 and the Cooling mode is
initiated in Heat Pump B (38ARQ012).
When the thermostat is satisfied, the contacts open, deener-
gizing first the Heat Pump B and then Heat Pump A.
Heating -- When the thermostat c_dls for heating, the circuit
from R to WI is completed. If the time delays and safeties are
satisfied, the compressor contactor closes, st_uting the com-
plessor and outdoor-fan motors of Heat Pump A and Heat
Pump B. At the same time the circuit is completed from R to G.
st_uting the indoor-fan motol: If the second stage of heating is
required, the circuit from R to W2 will be completed and the
electric lesistance heaters will be energized.
When the thermostat is satisfied, the contacts open, deener-
gizing Heat Pump A and Heat Pump B.
SAFETIES- The high-plessure switch, loss-of-charge
switch, oil pressure safety switch, and compressor overtemper-
ature safety are located in a CLO that prevents heat pump
operation if these safety devices are activated. The lockout
system can be reset by adjusting the thermostat to open the
contacts (down for Heating mode, up for Cooling mode), deen-
ergizing the CLO. Compressor overcurrent protection is
achieved with a circuit breaker which requires manual reset-
ting at the outdoor unit control box (38AQS only).
The 38AQS unit is equipped with an oil pressure safety
switch that protects the compressor if oil pressure does not de-
velop on start-up or is lost during operation. The oil pressure
switch is of the manual reset type and therefore must be reset at
the outdoor unit. DO NOT RESET MORE THAN ONCE.
If oil pressure switch trips, determine cause and correct. DO
NOT JUMPER OIL PRESSURE SAFETY SWITCH.
To reset the oil pressure switch:
1. Disconnect power to the unit.
2. Press the RESET button on the oil pressure switch.
3. Reconnect power to the unit.
Unit is equipped with a no-dump reversing valve circuit.
When unit is in Cooling mode, reversing valve remains in cool-
ing position until a call for heating is requested by themlostat.
When unit is in Heating mode, reversing valve remains in heat-
ing position until there is a call for cooling.
CHECK OPERATION -- Ensure operation of all safety con-
trois. Replace zfll service panels. Be sure that control panel
cover is dosed tigh@
Restart --Manu_fl reset of the 24-v control circuit is
necessa q if unit shutdown is caused by automatic reset devices
(including IP [internal compressor overcurrent protectionl,
HPS [high-pressure switchl, LCS [loss-of-charge switchl), or if
shutdown is caused by manual reset devices (including OPS
[oil pressure switchl and compressor circuit breaker protec-
tion). To restart the unit when IR HPS, or LCS has tripped (@
Wr device has reset automati_zd@), open and then close the
thermostat contacts. Opening and then closing thermostat con-
tacts interrupts and restores 24-v power to the CLO, which
resets the circuit.
It is necessary to manu_dly reset the compressor cimuit
breaker and OPS at the unit if either of these safeties should
shut down the unit.
IMPORTANT: If OPS trips, it must be reset fi_t before
making and b_eaking the thermostat contacts to reset
CLO. If this procedure is not followed, the CLO cannot
_eset.
Causes of Complete Unit Shutdown:
interruption of supplied power
open compressor overtemperature protection (IP)
compressor electrical overload protection (CB)
open high-pressure or loss-of-charge safety switches
open oil pressure switch
open crankcase heater lockout (CLO2)
open control circuit fuse (FUI or FU2)
open discharge gas thermostat (38ARQ only)
SERVICE
Compressor Removal -- See Tables IA-ID for com-
pressor information. Follow safety codes and wear safety
glasses and work gloves.
1. Shut off power to unit. Remove unit access panel.
2. Recover refrigerant from system using refrigerant recovery
methods described in C;urier Training booklet GTAC |I,
Module 5, and in accordance with loc:d and national
stan&_rds.
3. Disconnect compressor wiring at compressor termimd
box.
4. Disconnect refrigerant lines from compressol:
22
Page view 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 31 32

Comments to this Manuals

No comments