Carrier 38AQ Specifications Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
5. Remove screws fiom compressor mounting plate.
Excessive movement of copper lines at compressor may
cause higher levels of vibration when unit is restored to
service.
6. Remove or disconnect crankcase heater from compressor
base.
7. Remove compressor from unit.
8. On 38AQS016 unit remove compressor holddown bolts
and lift compressor off mounting plate.
9. Clean system. Add new liquid line filter &ier
10. Install new compressor on compressor mounting plate
and position in unit. Connect vapor and discharge lines to
compressor. Secure mounting plate with compressor to
unit. Ensure that compressor holddown bolts are in place.
Connect wiring. Install crankcase heatel:
11. Evacuate and rechmge unit.
12. Restore unit powel:
38ARQ008, 012 Cooling Mode Operation
(See Fig. 20)
1. High pressure, high temperature refrigerant vapor from
the compressor flows through the reversing v_flve and is
directed to the vapor headel:s of both outdoor coils.
2. At the outdoor coil vapor header, the high pressure, high
temperature refrigerant vapor flows up to check valve
"A" that blocks the flow. All the refrigerant is then
directed to flow into the coil circuits.
3. Subcooled refrigerant liquid leaves the coil circuits
through the side outlet on the liquid headers. The liquid
refrigerant from each coil flows through check valves
"B" which are open, enters the liquid line and goes to the
indoor coil.
4. The liquid refrigerant is expanded and evaporated in the
indoor coil resulting in low pressure vapol: This low
pressure vapor returns to the outdoor unit through the
system vapor line, reversing valve, and accumulatol:
reentering the compressor at the suction connection.
38ARQ008, 012 Heating Mode Operation
(See Fig. 21)
1. High pressure, high temperature refrigerant vapor from
the compressor flows through the reversing valve and
is directed through the system vapor line to the indoor
coil. Refrigerant is condensed and subcooled in the
indoor coil and returns to the outdoor unit through the
system liquid line.
2. Check valve "B" blocks the flow of liquid and the liquid
refrigerant must flow through the filter driers, through
check v_dve "C", and into the liquid header assembly.
3. The liquid refrigenmt is expanded as it passes through the
fixed orifice metering devices into outdoor coil circuits.
The refrigerant evaporates as it passes through the coil
circuits resulting in low plessure vapol:
4. The low pressure vapor leaves the coil circuits and enters
the vapor headers, check valves "A" are open, and returns
to the compressor through the vapor line, revelling valve,
and accumulator, reentering the compressor at the suction
connection.
COMPRESSOR _ REVERSING VALVE
_M ULAT4(_OR _ VAPO_'_RLINE
vel
FIXED ORIFICE
METERING DEVICE
FILTER
DRIER
LIQUID LINE
Fig. 20 -- 38ARQ008, 012 Cooling Mode (Size 008 Shown)
FROM
[_]ZZZ1 INDOOR
UNIT
BALL
VALVE
TO
[_INDOOR
UNIT
BALL
VALVE
23