Carrier 50HCQA Installation Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
18
Constant Volume (CV) Units (FTYP = 1--Speed)
Single speed fan units are controlled by the Indoor Fan Relay 1
(Outputs FANS IDF.1) on the main base board (MBB),
which then operates the indoor fan contactor (IFC). The fan will be
either on or off depending on the unit control type and the
conditions above.
Thermostat Control
In thermostat mode, the IDF relay will be on in the following
situations: fan request G in ON, cooling request Y1 or Y2 is ON,
or heating request W1 or W2 is ON. If the G call is dropped or was
never on with an Y1, Y2, W1, or W2 call; the IDF relay will turn
off after a configurable time delay with respect to the HVAC mode
that is ending.
Space Sensor Control
In Space Sensor mode, the IDF relay will be on if the unit is in
Occupied mode and the indoor fan is configured to always run while
occupied (Configuration I.FAN OC.FN = YES). If the indoor
fan is configured for intermittent fan (OC.FN = No), the fan will only
be on when there are cooling, heating, or dehumidification stages
running; or if there is an air quality demand. During the unoccupied
period, the fan will operate intermittent. With intermittent fan, the IDF
relay will turn off after a configurable time delay with respect to the
HVAC mode that is ending.
Cooling Operation
The 48/50HC units cooling operation consists of: demand, mode
determination, staging request to satisfy the demand, and handling
a request with the unit’s resources. These resources can include
compressors, an economizer, and a reheat coil. This section covers
mechanical cooling. For economizer and reheat cooling, refer to
the Economizer and Humidi--MiZert sections, respectively. The
unit enters a cooling mode based on a demand, decides how to
satisfy the demand, executes its plan, and then leaves the cooling
mode.
Cooling Mode Control
The cooling HVAC mode (Run StatusMODEHVAC=3)has
six different expandable texts: Cooling, Free Cooling, Unoccupied
Free Cooling, Reheat1, Reheat2, or Reheat1/Reheat2. These are all
part of a general cooling mode and resemble the specific type of
cooling that is being performed at any given time. All types of
cooling are still performed under the general cooling function, and
the expanded text is for user reference only. The control will
display if it is ok to select the cooling mode (Operating Modes
COOLOK.CL= Yes).
Thermostat Control
For the unit to enter cooling mode, three things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, and there must be a cooling demand (Y1, Y2, or
dehumidification demand). The unit will remain in cooling until
the cooling demand is dropped or if any of the above conditions
turn false. If only a dehumidification demand exists and a heat
demand (W1, W2) occurs, the unit will end cooling. The cooling
mode can not officially end until all compressors are off.
Space Sensor Control
For the unit to enter cooling mode, four things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, the unit must have a valid space temperature, and
there must be a cooling or dehumidification demand. The unit will
remain in cooling for at least one minute and until the cooling
demand drops below --0.5_F or if any of the above conditions turn
false. If only a dehumidification demand exists and the heat
demand becomes greater than the Reheat Heat Setpoint Deadband
(SetpointsRH.HB), the unit will end cooling. The cooling mode
can not officially end until all compressors are off.
Staging Control
Once the unit is in a cooling mode, it must decide what the demand
is and how to satisfy it. If an economizer is installed and can be
used for cooling (Operating ModesCOOLOK.EC= Yes), the
unit will use it first (see economizer section for its operation). If
the economizer can not be used or additional cooling is needed, a
mechanical cooling check is performed. OK to use Compressors?
(Operating ModesCOOLOK.MC), will be set to yes when
compressors are enabled and not locked out. Based on the unit
control configuration, requested cooling stages (Run Status
COOLREQ.C) will be determined then passed to compressor
control to actually add the cooling stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is
enabled, Traditional Thermostat control or Adaptive control.
Traditional Thermostat control is used if the Thermostat Control
Type (T.CTL) is set to 1, 2, or 3 and the economizer is not
available for free cooling. If Thermostat Control (T.CTL) is set to
0 or any time the economizer is available for free cooling, the unit
will use Adaptive control for staging.
T.CTL = 0 (Adaptive Control)
Stage timers, Supply air trend, and supply air temperature limits
apply when determining the request for stages. The first request
(REQ.C=1) comes immediately when the Y1 input is active. The
CoolStageIncreaseTime(ConfigurationCOOLC.INC)or
the Cool Stage Decrease Time (ConfigurationCOOLC.DEC)
has to expire before another stage can be added or a stage can be
subtracted. The Supply--Air Trend (Operating
ModesCOOLSA.TR) decides if the next stage can be
requested or should be subtracted based on the Y2 input status.
If the Y1 and Y2 inputs are dropped, the supply air trend is not
considered because cooling is no longer needed. If at any time
the Supply--Air Temperature (SAT) falls below the Minimum
Supply Air Temperature Upper Level (Configuration
COOLSATSAT.U), the requested stages will not be
allowed to increase. If at any time the SAT falls below the
Minimum Supply Air Temperature Lower Level (Configuration
COOLSATSAT.L), the requested stages will be reduced by
one without honoring C.DEC. If SAT.L and SAT.U are configured
so that they are close together, the last stage of compressor might
cycle rapidly, slowed only by its minimum on and off--time
requirements.
T.CTL=1(1StageY1)andT.CTL=2(2StageY1)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one
stage. Y2 will request all stages.
T.CTL = 3 (Digital)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one stage.
Y2 will request two stages. Y1 and Y2 will request all stages.
Space Sensor Control
Space sensor staging control is an adaptive anticipation control that
weighs the actual space demand against the trend of that demand
and the trend of the supply air. It also honors stage time guards
and supply air limits. The demand for cooling in the space is
displayed as the Cooling Demand (Run StatusCOOL
DMD.C). The control tries to anticipate the change in the space
because of its current stage status. This anticipation is based on the
Supply--Air Trend (Operating ModesCOOLSA.TR)andthe
Cool Demand Trend (Operating ModesCOOLTRD.C).
These trends will show the control how the space is reacting to the
current running conditions and help it decide when to add or
remove one stage from the requested stages. The Cool Stage
Increase Time (ConfigurationCOOLC.INC) or the Cool
Stage Decrease Time (ConfigurationCOOLC.DEC)hasto
ComfortLINK v2.X
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 103 104

Comments to this Manuals

No comments