Carrier 50HCQA Installation Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
25
Sensor Value at 4ma (ConfigurationAIR.QH.4M)setsthe%
display for a 4mA input from the relative humidity sensor. RH
Sensor Value at 20ma (ConfigurationAIR.QH.20M)setsthe
% display for a 20mA input from the relative humidity sensor.
Dehumidification Demand
When using a humidistat or switch input, the demand for
dehumidification is seen as Space Humidity Switch (Inputs
GEN.IHUM) being Low or High. A low value means
humidity level is good and a high value means that
dehumidification is needed. When using an RH sensor, the demand
is based on the Space Humidity Sensor (InputsAIR.QSP.RH)
value compared to the Space RH Occupied Setpoint
(SetpointsRH.SP) during the occupied period and Space RH
Unoccupied Setpoint (Setpoints RH.UN) during unoccupied
periods. If the Space Humidity Sensor (SP.RH) value is above the
Space RH Setpoint (RH.SP), then dehumidification is needed. If
the Space Humidity Sensor (SP.RH) value is below the Space RH
Setpoint (RH.SP) minus the Space RH Deadband
(SetpointsRH.DB), then dehumidification is no longer needed.
If the unit is configured for space sensor control
(ConfigurationUNIT U.CTL = 3), then the setpoint Reheat
Heat SP Deadband (SetpointsRH.HB) applies. This
configuration sets the offset above the heating set point at which a
unit in Reheat2 mode will turn off. This is a protection against over
cooling the space and causing a heat demand.
NOTE: When there is a dehumidification demand, the economizer
damper position is limited to it’s minimum damper position
(Operating ModeECONEC.MP).
Reheat Modes
Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With Humidi--MiZer
units there are three additional HVAC Mode (HVAC) expanded
texts available for the user: Reheat1, Reheat2, and
Reheat1/Reheat2. Selection of the reheat mode for each refrigerant
circuit is determined by the dehumidification demand and the
cooling demand. Table 8 shows the corresponding circuit mode
and output status for the different demand combinations. Units
with multiple circuits can operate with a combination of Reheat1
and Reheat2 circuits, as determined by the amount of space cooling
demand. See Appendix B for complete tables of unit operation
response to thermostat and humidity inputs.
NOTE: Compressor staging control for Humidi--MiZer units
requires that circuit A always operates when circuit B is on. This
applies to normal operation, service test, and for control alarm
responses. This operation difference is required due to the fact that
the Motormaster outdoor fan control senses circuit A only.
Operation of the revised refrigerant circuit for each mode is
described below.
NOTE: x = refrigerant circuit A or B
Normal Cooling
For 48/50HC04--12 units, refrigerant flows from the outdoor
condenser through the normally open Cooling Liquid Valve
(CLV.x) to the expansion device. Reheat Liquid Valve (RLV.x) and
Reheat Discharge Valve (RDV.x) are closed. (See Fig. 9.)
For 48/50HC14--28 units, refrigerant flows from the outdoor
condenser through the de--energized 3--way Liquid Diverter Valve
(LDV.x) to the expansion device. Reheat Discharge Valve (RDV.x)
is closed. (See Fig. 12.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible cooling
compared to normal cooling.
For 48/50HC04--12 units, refrigerant flows from the outdoor
condenser, through the normally open Reheat Liquid Valve
(RLV.x), and through the reheat condenser coil to the expansion
device. Cooling Liquid Valve (CLV.x) and Reheat Discharge Valve
(RDV.x) are closed. (See Fig. 10.)
For 48/50HC14--28 units, refrigerant flows from the outdoor
condenser, through the energized 3--way Liquid Diverter Valve
(LDV.x), and through the reheat condenser coil to the expansion
device. Reheat Discharge Valve (RDV.x) is closed. (See Fig. 13.)
Reheat 2 (Hot Gas Reheat Mode)
This mode provides maximum latent cooling with little to no sensible
capacity. This mode can operate to provide dehumidification when
there is no cooling demand. Similar to Reheat 1 mode, refrigerant
flows from the outdoor condenser, through the normally open Reheat
Liquid Valve (RLV1.x), or through the energized 3--way Liquid
Diverter Valve (LDV.x), and through the reheat condenser coil to the
expansion device. Reheat Discharge Valve (RDV.x) is open which
provides some compressor discharge gas to the reheat condenser to
further increase the reheat of the evaporator air stream (See Fig. 11 or
14 based on unit and size).
Table 8 – Control Modes with Humidi--MiZert System
Output and Valve States versus Circuit Mode .x = Circuit A or B identifier
DEMAND AND MODE OUTPUTS 48/50HC 04--- 12 VALVES 48/50HC 14--- 28 VALVES
Space
Humidity
Circuit
Cooling
Demand
Circuit
Mode
Circuit
Compressor
(CMP.x)
Cooling---
Reheat
Control
(CRC)*
Reheat2
Valve
(RH2.x)
CLV.x
Valve
2 --- w a y
RLV.x
Valve
2---way
RDV.x
Valve
2 --- w a y
RLV.x
Valve
3---way
RDV.x
Valve
2---way
No power Off Off Off
Off
(open)
Off (open)
Off
(closed)
Off
Off
(closed)
Low No Off Off Off Off
Off
(open)
On
(closed)
Off
(closed)
Off
Off
(closed)
Low Ye s C ool On Off Off
Off
(open)
On
(closed)
Off
(closed)
Off
Off
(closed)
High Ye s Reheat1 On On Off
On
(closed)
Off (open)
Off
(closed)
On
Off
(closed)
High No Reheat2 On On On
On
(closed)
Off (open)
On
(open)
On On (open)
ComfortLINK v2.X
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 103 104

Comments to this Manuals

No comments