APPENDIX A LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATION
ITEM EXPANSI O N RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO .
CONFIGURATION SERVICE
CONFIGURATION
DISP DISPL AY CONFIGURATION DISPLAY
METR Metric Display No/Y es No DISPUNIT 14
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE 14
PROT Password Enable Disable/Enable Enable PASS_ EBL 14
PSWD Service Password 0000 to 9999 1111 PASSWORD 14
TEST Test Display LEDs Off/On Off (display only,
not in table)
DISPTEST 14
UNIT UNIT CONFIGURATION UNIT
S.DLY Startu p Delay 10 to 600 sec 30 STARTDL Y 14
U.CTL Unit Control Type 2=Thermostat
3=Space Sensor
2 CTL_TYPE 14
T. C T L Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STA TTYPE 14
FN.SW F an S tatu s S wi tc h 0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG 14
FL.SW Filter Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 FILS T C FG 14
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 14
RM.SW Remote Occupancy Swi tc h 0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 14
SAT.T SA T Settling Time 10 to 900 sec 240 SAT_SET 14
RAT.S RAT Sensor Installed No/Y es No RA T _SEN S 14
RH.S RH Sensor on OAQ Input No/Y es No RH_OAQ 14
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG 14
TCS.C Temp Cm p S trt Cool Fac tr 0to60 mins 0 TCST COOL 14
TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT 14
I.FAN INDOOR FAN CONFIG AFAN_CFG
FTYP In door F an Type 0 = 1 --- S P E E D
1=LEN VFD
0
1: SAV option
FAN_TYPE 16
NSPD Num ber of Speeds 2, 3, or 7 2 NUM_SPDS 16
OC.FN FanOnWhenOccupied No/Y es Yes OCC_FAN 17
IDF.F Shut Down on IDF Failure No/Y es Yes FAT ALFAN 16
FS.MX Su pply Fan Maximum Speed 80 t o 100 100 SPEEDMAX 17
FS.VN Fan Speed --- V entilation 0 to 100 % 67 FS PDV E N T 17
FS.AQ Fan Sp eed --- IAQ Overrid e 0 to 100 % 100 FSPD AQOR 17
FS.E1 Fan Speed --- Free Cool Lo 0 t o 100 % 67 FSPDEC O1 17
FS.CL F an S peed --- Mech Cool in g 60 to 100 % 67 FSPDCOOL 17
FS.RH Fan Speed --- Reheat2 65 t o 100 % 100 FSPDRE HT 17
S.VFD SUPPLY FAN VFD CONFIG
N.VLT VFD 1 Nom in al M otor V ol ts 0 to 999 volts 230: 208/230v 1ph or 3ph
460: 460v
575: 575v
VFD1NVL T
N.AMP VFD 1 Nomi n al Motor Am ps 0 to 999 amps See VFD Motor Param eters tabl e VFD1NAMP
N.FRQ V FD1 Nom in al Motor Freq 10 to 500 60 VFD1NFRQ
N.RPM VFD1 Nom in al M otor RPM 50 to 30000 S ee VFD Motor Par ameters tabl e VFD1NRPM
N.PWR VFD1 Nom in al M otor HPwr 0 to 500 See VFD Motor Par ameters tabl e VFD1NPWR
MAX.A VFD1 Maximum Amps 0 to 999 amps See VFD M otor Par ameters tabl e VFD1MAXA
M.DIR VFD1 Motor Dire c tion 0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL VFD1 Acceleration Time 0 t o 1800 secs 30 VFD1ACCL
DECL VFD1 Deceleration Time 0 to 1800 secs 30 VFD1DECL
SW.FQ VFD1 Switching Frequency 0to3 2 VFD1SWFQ
ComfortLINK v2.X