APPENDIX A LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
RUN STATUS STATUS DISPLAY
VIEW Auto View of Run Status (VIEW = Display only)
HVAC HVAC Mode Status
1=Disabled
2=Ventilation
3=Cool
4=Heat
HVACMODE
OCC Currently Occupied No/Yes OCCUPIED
SAT Supply Air Temperature xxx..x _F SAT_DISP
ALRM Current Alarms & Alerts xx ALRMALRT
TIME Time of Day xx.xx hh.mm TIMECOPY
VERS Software Version Numbers VERSIONS
MBB CESR131504---xx--- xx ( x x --- x x i n t a b l e ) MODEL_NUMBER_01
ECB CESR131249 --- xx---xx MODEL_NUMBER_02
MARQ CESR131171---xx---xx MODEL_NUMBER_03
VFD1 FW Version --- xxxx MODEL_NUMBER_04
NAVI CESR131227--- xx--- xx
MODE Control Modes MODEDISP
SYS Current System Mode 1=Disabled
2=Run Enabled
3: Service Test
SYS_MODE
HVAC Current HVAC Mode 1=Disabled
2=Ventilation
3=Cool
4=Heat
HVACMODE
F. M O D Indoor Fan Mode 0=Off
1=High
2=Low Cool
3=Vent
4=IAQ Override
5=Low Heat
6=Dehum
7=Low Free Cool
IDF_MODE
HV.DN Remote HVAC Mode Disable No/Yes HVACDOWN forcible
EFF.C Cool Setpoint In Effect xx.x _F CSP_EFF
EFF.H Heat Setpoint In Effect xx.x _ F HSP_EFF
OCC Currently Occupied No/Yes OCCUPIED forcible
T. O V R Timed Override in Effect No/Y es MODETOVR
LINK Linkage Active No/Y es MODELINK
D.LMT Demand Limit In Effect No/Yes MODEDMDL
C.LOC Compressor OAT Lockout No/Yes COMPLOCK
H.LOC Heat OAT Lockout No/Yes HEATLOCK
OK.EC OK to Use Economizer? No/Yes ECONCOOL
COOL Cooling Status COOLDISP
DMD.C Cooling Demand xxx.x ^F COOL_DMD
AVL.C Available Cooling Stages x AVLCSTGS
REQ.C Requested Cooling Stages x REQCSTGS
MAX.C Max Allowed Cool Stages x MAXCSTGS forcible
LMT.C Max Cool Stage In Effect x CSTGLIMT
F.SPD Commanded Fan Speed xxx % FANSPEED
CRC Cool --- > Reheat1 Control Off/On CRC
CIR.A Refrigerant Circuit A
CMP.A Circuit A Compressor Off/On COMP_A
TG.A Timeguard A xxx sec TIMGD_A
RH2.A Reheat2 Valve A Off/On RH2_A
SST.A Sat. Suction Temp A xxx.x _F SST_A
SSP.A Suction Pressure A xxx.x psig SSP_A
SCT.A Sat. Condenser Temp A xxx.x _F SCT_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
CIR.B Refrigerant Circuit B
CMP.B Circuit B Compressor Off/On COMP_B
TG.B Timeguard B xxx sec TIMGD_B
RH2.B Reheat2 Valve B Off/On RH2_B
SST.B Sat. Suction Temp B xxx.x _F SST_B
SSP.B Suction Pressure B xxx.x psig SSP_B
SCT.B Sat. Condenser Temp B xxx.x _F SCT_B
SCP.B Condenser Pressure B xxx.x psig SCP_B
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
LMT.H Max Heat Stage In Effect x HSTGLIMT
F.SPD Commanded Fan Speed xxx % FANSPEED
HT.1 Heat Stage 1 Relay Off/On HEAT_1
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
ComfortLINK v2.X