APPENDIX A LOCAL DISPLAY AND CCN TABLES
MODE — OPERATING MODES (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN
WRITE
STATUS
DISPLA Y
WRITE
STA TUS
COOL (cont) Cool Mode Diagnostic COOLDIAG
R.LP.B Reheat2 SSP Override B No/Yes RHBLPOV
AVL.R Available Reheat2 Stages x AVLRSTGS
REQ.R Requested Reheat2 Stages x REQRSTGS
ACT.R Actual Reheat2 Stages x ACTRSTGS
CRC Cool--->Reheat1 Control Off/On CRC
RH2.A Reheat2 Valve A Off/On RH2_ A
RH2.B Reheat2 Valve B Off/On RH2_B
HEAT Heat Mode Diagnost ic HEATDIAG
HEAT In Heating Mode? No/Y es IN_HEAT
OK.HT OK to Select Heat Mode? No/Yes OKTOHEAT
MS.TG Mode Select Timeguard xxx secs HEATMSTG
H.LOC Heat OAT Lockout No/Yes HEATLOCK
HT.LO Heating Lockout Temp xxx °F OATLHEAT
IGC.F IGC Fan Request IDF_FDBK
F. M O D Indoor Fan Mode x IDF_MODE
F.SPD Commanded Fan Speed xxx % FANSPEED
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
LMT.H Max Heat Stage In Effect x HSTGLIMT
ACT.H Actual Heating Stages x ACTHSTGS
HT.1 Heat Stage 1 Relay Off/On HEAT_1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
SAT Supply Air Temperature
SAT.H SAT Heat Mode Sensing Disable/Enable SAT_HEAT
SAT Supply Air Temperature xxx.x °F SAT_DISP
SAM.L Maximum SAT Lower Level xxx.x °F SATMAX_L
SAM.U Maximum SAT Upper Level xxx.x °F SATMAX_H
SPT Space Temperature
SPT Space Temperature xxx.x °F SP ACE_T forcible forcible
DMD.H Heating Demand xxx.x ^F HEAT_DMD
TRD.H Heat Demand d/dt (F/min) xxx.x HTDTREND
HT.PD SPT Heat Demand (+) Level xx.x ^F HDEM_POS
HT.ND SPT Heat Demand (--- ) Level xx.x ^F HDEM_NEG
H.LAG Heat Thermal Lag Factor x.x HEAT_LAG
ECON Economizer Diagnostic ECONDIAG
EC.EN Economizer Installed No/Y es ECONO
OK.EC OK to Use Economizer? No/Yes ECONCOOL
OCC Currently Occupied No/Yes OCCUPIED forcible forcible
F. M O D Indoor Fan Mode x IDF_MODE
F.SPD Commanded Fan Speed xxx % FANSPEED
COOL In Cooling Mode? No/Yes IN_COOL
OAT Outdoor Air Temperature xxx.x °F OA_TEMP forcible forcible
RAT Return Air Temperature xxx.x °F RETURN_T forcible
E.LOC Econo Cool OAT Lockout No/Yes ECONLOCK
D.LOC Econo Diff Dbulb Lockout No/Yes DFDBL OCK
EH.LO Econo Cool H i Temp Limit xxx °F OATLECLH
EL.LO Econo Cool Lo Temp Limit xxx °F OATLECLL
FC.LO Free Cool Low Temp Limit xxx °F OATLUEFC
EN.LO Econo Cool Enth Lockout No/Yes ENTHLOCK
EC.MX Econo Cool Max Position xxx % ECONOMAX
AQ.DV IAQ DCV Mode No/Y es IN_IAQDV
AQ.MN Econo Min IAQ Position xxx % IAQMINP
AQ.OV IAQ Override Mode No/Yes IN_IAQOV
OVR.P IAQ Override Position xxx % IAQOVPOS
AQ.LO OAQ Lockout Mode No/Y es IN_OAQLO
OAQ.L OAQ Lockout Limit xxxx OAQLOCK
LP.OV Lo Refrig Press Override No/Yes IN_LPOV
EC.CP Econo Commanded Position xxx % ECONOCMD forcible forcible
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP MinPositioninEffect xxx % MIN_POS forcible forcible
C.ANG Actuator Control Angle xx.x CTLANGLE
E.CAL Economizer Calibrating No/Y es ECOINCAL