Carrier 50HCQA Installation Manual Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
29
Reheat Control
The cooling staging and compressor control routines are
responsible for controlling each circuit in one of the three
sub--modes (Cool, Reheat1, or Reheat2). When there is only a
cooling demand, one or more circuits will operate in normal
cooling mode. When there is only dehumidification demand, all
circuits will operate in Reheat2 mode. When there is both cooling
demand and dehumidification demand, all circuits will operate in
either Reheat1 or Reheat2 mode, with the portion of Reheat1
circuits determined from the cooling demand. The Requested
Reheat2 Stages (Operating ModesCOOLHMZRREQ.R)
shows the control’s request for reheat circuits if cooling is not
already requesting all stages. Available Reheat2 Stages (Operating
ModesCOOLHMZRAVL.R) displays circuits that are
available for reheat use. Actual Reheat2 Stages (Operating
ModesCOOLHMZRACT.R) displays the current number
of circuits running in Reheat2 mode. These three status points
should only be monitored when there is only a dehumidification
demand, because their values can be forfeited to cooling stages
when cooling demand is present. Reheat2 Stage Incr. Time
(ConfigurationHMZR R.INC) and Reheat2 Stage Decr. Time
(ConfigurationHMZRR.DEC) set the time delay when
adding or subtracting a compressor for a reheat function. These
only apply when using adaptive thermostat or space sensor control.
There are three relay outputs that show reheat status. Cool -- >
Reheat1 Control (OutputsCOOLCRC) show when the unit
has switch from pure cooling to reheat ready (based on a
dehumidification demand). Reheat2 Valve A
(OutputsCOOLRH2.A) and Reheat2 Valve B
(OutputsCOOLRH2.B) display when the respective circuit’s
Reheat2 valve is energized.
A circuit can be restricted from Reheat2 operation by the outside
temperature and saturated suction temperature. Reheat2 OAT
Limit A (ConfigurationHMZRRA.LO) and Reheat2 OAT
Limit B (ConfigurationHMZRRB.LO) set the lowest outside
temperature the respected circuit is allowed to run in reheat2 mode.
The lockout on/off status is shown as Reheat2 OAT Lockout A
(Operating ModesCOOLHMZRR.LO.A) and Reheat2
OAT Lockout B (Operating ModesCOOLHMZR R.LO.B)
for their respective circuit. If a circuit’s saturated suction pressure
falls below the low limit configuration during Reheat2 operation,
the circuit will switch to reheat1 (the circuits Reheat2 valve will be
turned off) for at least 2 minutes and until its suction rises back
above the high limit. Reheat2 SSP Lo Limit A
(ConfigurationHMZRRA.LP) and Reheat2 SSP Lo Limit B
(ConfigurationHMZRRB.LP) set the low pressure limit for
Reheat2 mode for individual circuits. Reheat2 SSP Hi Limit A
(ConfigurationHMZRRA.HP) and Reheat2 SSP Hi Limit B
(ConfigurationHMZRRB.HP) set the high pressure limit for
Reheat2 mode for each circuit.
Reheat Mode Diagnostic Help
The status of reheat mode sensor inputs may be viewed within the
display Inputs menu. The status of reheat mode outputs may be
viewed within the display Outputs or Run StatusCOOL menus.
Additional diagnostic help, including status of circuit reheat
temperature limit lockouts may be viewed within the
Humidi-MiZer sub-menu of the cooling mode diagnostic table at
Operating ModesCOOLHMZR.
The Service Test mode may be used to force the system to operate
in various stages of Reheat1 or Reheat2 mode, or to independently
operate the reheat valve control outputs.
The following forced operating states are changed or added to the
available service test operation for a Humidi-MiZer equipped unit:
Service TestCOOLCMP.A (Cool A Test)
A value of On will turn on circuit A in Normal Cooling mode.
Service TestCOOLCMP.B (Cool B Test)
A value of On will turn on circuits A and B in Normal Cooling mode.
Service TestHMZRRH1.A (Reheat1 A Test)
A value of On will turn on circuit A in Reheat1 mode.
Service TestHMZRRH1.B (Reheat1 B Test)
A value of On will turn on circuits A and B in Reheat1 mode.
Service TestHMZRRH2.A (Reheat2 A Test)
A value of On will turn on circuit A in Reheat2 mode.
Service TestHMZRRH2.B (Reheat2 B Test)
A value of On will turn on circuits A and B in Reheat2 mode.
Service TestHMZRCRC (Cool-Reheat1 Valve Test)
For 48/50HC04--12 units, a value of On will turn on the CRC
relay. This will turn on CLV.x valves and turn off RLV.x valves.
For 48/50HC14--28 units, a value of On will turn on the CRC
relay. This will energize the LDV.x valves.
Service TestHMZRRHV.A (Reheat2 Valve A Test)
A value of On will turn on the RDV.A valve.
Service TestHMZRRHV.B (Reheat2 Valve B Test)
A value of On will turn on the RDV.B valve.
EnergyX
For units equipped with the EnergyX factory installed option, there
will be an EnergyX Supplement Installation Instructions in the
units information packet. Refer to this supplement for details on
how the ERV operates relative to the base unit.
Temperature Compensated Start
This logic is used when the unit is in the unoccupied state. The
control will calculate early Start Bias time based on Space
Temperature deviation from the occupied cooling and heating set
points. This will allow the control to start the unit so that the space
is at conditioned levels when the occupied period starts. This is
required for ASHRAE 90.1 compliance. A space sensor is required
for non-linkage applications.
Setting Up the System
The settings for temperature compensated start can be found in the
local display under ConfigurationUNIT.
ITEM EXPANSI O N RANGE UNI TS CCN POINT
TC S.C Temp.Cmp.Strt.Cool Factr 0-60 min TC STCOOL
TC S.H Temp.Cmp.Strt.Heat Factr 0-60 min TCSTHEAT
Temp Comp Strt Cool Factr (TCS.C)
This is the factor for the start time bias equation for cooling.
Temp Comp Strt Heat Factr (TCS.H)
This is the factor for the start time bias equation for heating.
NOTE: Temperature compensated start is disabled when these
factors are set to 0.
Temperature Compensated Start Logic
The following conditions must be met for the algorithm to run:
S Unit is in unoccupied state.
S Next occupied time is valid.
S Current time of day is valid.
S Valid space temperature reading is available (sensor or CCN
network).
The algorithm will calculate a Start Bias time in minutes using the
following equations:
If (space temperature > occupied cooling set point)
Start Bias Time = (space temperature occupied cooling set
point)* TCS.C
If (space temperature < occupied heating set point)
Start Bias Time = (occupied heating set point space
temperature)*TCS.H
ComfortLINK v2.X
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 103 104

Comments to this Manuals

No comments