Humidi--MiZert Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view
the cooling status display and the cooling diagnostic display (see
Appendix A) for information on the cooling operation and the
related Humidi-MiZer operation. Check the current alarms and
alarm history for any cooling alarm codes and correct any causes.
(See Table 9.) Verify any unique control configurations per
installed site requirements or accessories.
If alarm conditions are corrected and cleared, operation of the
compressors, fans, and Humidi-MiZer valves may be verified by
using the Service Test mode (see Table 4.) In addition to general
cooling service analysis (see Table 11), see Table 12 for general
Humidi-MiZer service analysis.
NOTE: Wiring, operation, and charge are different on a
Humidi-MiZer unit compared to a standard unit.
Table 12 Humidi-MiZer Service Analysis
PROBLEM CAUSE REMEDY
Subcooling Reheat Mode
Will Not Activate.
General cooling mode problem. See Cooling Service Analysis (Table 11).
No dehumidification demand. See No Dehumidification Demand, below.
CRC relay operation. See CRC Relay Operatio n, below.
Ci rcuit RLV, CLV or LDV valve proble m. Se e CLV, RLV or LD V Valve Operation, below.
Hot Gas Reheat Mode
Will Not Activate.
General cooling mode problem. See Cooling Service Analysis (Table 11).
No dehumidification demand. See No Dehumidification Demand, below.
CRC relay operation. See CRC Relay Operatio n, below.
Ci rcuit RLV, CLV or LDV valve proble m. Se e CLV, RLV or LD V Valve Operation, below.
Circuit RDV valve is not open. SeeRDVValveOperation,below.
Outdoor temperature t oo low.
Check Reheat2 Circuit Limit Temperatures
(ConfigurationHMZRRA.LO and RB.LO)
using ComfortLink Scrolling Marquee.
No Dehumidification Demand.
Relative humidity setpoint is
too low Humidistat
Check/reduce setting on accessory humidistat.
Relative humidity setpoint is
too low RH sensor.
Check Space RH Setpoints (SetpointsRH.SP and RH.UN) and
occupancy using ComfortLink Scrolling Marquee.
Software configuration error
for accessory humidistat.
Check Space Humidity Switch (Configuration
UNITRH.SW) using ComfortLink Scrolling Marquee.
Software configuration error
for accessory humidity sensor.
Check RH Sensor on OAQ Input (Configuration
UNITRH.S) using ComfortLink Scrolling Marquee.
No humidity signal. Check wiring. Check humidistat or humidity sensor.
CRC Relay Operation.
No 24V signal t o input terminals.
Check using CoolReheat1 Valve Test (Service TestHMZRCRC)
using ComfortLink Scrolling Marquee.
Check MBB relay output.
Check wiring.
Check transformer and circuit breaker.
No power to output terminals. Check wiring.
Relay outputs do not change state. Replace faulty relay.
RLV, CLV or LDV Valve Operation
No 24V signal t o input terminals.
Check using CoolReheat1 Valve Test (Service TestHMZRCRC)
using ComfortLink Scrolling Marquee.
Check CRC Rela y Operation.
Check Wiring.
Check transformer and circuit beaker or fuses.
Solenoid coil burnout.
Check continuous over-voltage is less than 10%.
Check under-voltage is less t han 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
Stuck valve. Replace valve. Replace filter drier.
RDV Valve Operation.
(NOTE: Normally Clo s ed
When De-energized)
No 24V signal t o input terminals.
Check using CoolReheat1 Valve Test (Service TestHMZRRH V.A or
RHV.B) using ComfortLink Scrolling Marquee.
Check MBB relay output.
Check wiring.
Check transformer and circuit breaker or fuses.
Solenoid coil burnout.
Check continuous over-voltage is less than 10%.
Check under-voltage is less t han 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
Stuck valve. Replace valve. Replace filter drier.
Low Latent Capacity in Subcooling or
Hot Gas Reheat Modes.
CLV valve open or leaking. SeeCLVValveOperation,above.
Low Sensible Capacity in Normal Cool
or Subcooling Reheat Modes.
RDV valve open or leaking. SeeRDVValveOperation,above.
Low Suction Pressure and High
Superheat During Normal Cool Mode.
General cooling mode problem. See Cooling Service Analysis (Table 11).
RDV valve open or leaking. SeeRDVValveOperation,above.
Low Suction Pressure
and High Discharge Pressure.
General cooling mode problem. See Cooling Service Analysis (Table 11).
BothRLVandCLVvalvesclosed. Se e RLV and CLV Valve Operation, a bo ve.
RDV Valve Cycling On/Off.
Hot Gas Reheat mode low suction pressure limit.
Normal Operation During Mixed Circuit Subcooling and Hot Gas Reheat
Modes at Lower Outdoor Temperatures.
CircuitBWillNotOperateWith
Circuit A Off.
Normal operation. Motormaster outdoor fan con-
trol requires operation of circuit A.
None
LEGEND
CRC --- Cooling/Reheat Control
CLV --- Cooling Liquid Valve
RLV --- R e h e a t L i q u id V a l v e
RH --- Relative Humidity
RDV --- Reheat Discharge Valve
ComfortLINK v2.X