Aquazone™ water source heat pump products are available
in a flexible, efficient array of models, which can be used in
all types of water loop, ground water, and ground loop
type systems. Utilize Aquazone products to provide opti-
mal energy efficient solutions and adapt to the most chal-
lenging design requirements.
AQUAZONE PRODUCT GUIDE
Water loop system
Water loop (or boiler/tower) system applications typically
include a number of units plumbed to a common piping
system. For optimal performance, this system should be
designed between 2.25 and 3 gpm per ton of cooling ca-
pacity. The system is comprised of highly efficient pack-
aged reverse cycle heat pump units interconnected by a
water loop. The water circuit serves as both a sink and
source for heat absorption and rejection and is designed
for entering water temperatures between 60 F and 90 F.
Within this temperature range units can heat or cool as re-
quired from the same water source. Transferring heat from
warm to cold spaces in the building, whenever they coex-
ist, conserves energy rather than creating new heat.
Refer to the Carrier Water Source Heat Pump Sys-
tem Design Guide for assistance with the design of water
loop systems. The guide includes a practical approach for
the latest and most current design recommendations
including:
Product application including horizontal, vertical, con-
sole, rooftop and water-to-water applications.
Ventilation methods and system design including energy
recovery.
Acoustical considerations for different product types.
Addressing indoor air quality (IAQ) issues such as con-
densate removal, humidity control.
Air distribution design including diffuser selection/
layout and ductwork design.
Hydronic system design including pipe sizing/layout
and boiler/tower sizing.
Control configurations such as stand alone, DDC, DCV,
and VVT
®
controls.
WSHP Efficiency/Operational Cost Comparison chart.
System variations such as a system without a boiler,
variable pumping, and VAV for interior use.
Ground water systems
To utilize Aquazone units in ground water applications, ex-
tended range should be specified. This will provide factory-
installed insulation on the coaxial coil to prevent conden-
sate from dripping when entering water temperatures are
below 60 F. In addition, the copper coaxial coil installed on
the Aquazone units may not be suitable for all water condi-
tions. Refer to the Water Conditioning section for proper
coaxial coil material selection.
Surface water system — This system is typically located
near a lake or pond. In this application, the loop can be
submerged in a series of coils beneath the water surface.
The number of coils required depends on system load and
design. This application requires minimum piping and
excavation.
Open loop system — This system is used where ground
water is plentiful. In this application, ground water is
pumped through supply piping from the well to the building.
The water is then pumped back into the ground through a
discharge well as it leaves the building. An additional heat
exchanger is usually installed between the building water
piping system and the ground water piping system. This de-
sign limits the amount of piping and excavation required.
Aquazone units are provided with a standard TXV and
are rated to extremely low temperatures to self-adjust the
refrigeration circuit, therefore water regulating valves are
not required on open loop systems. To conserve water on
this type of system, a slow opening/closing solenoid valve
is recommended.
Ground loop systems
There are many commonly specified designs for ground
loop applications. Typical designs include vertical loops
and horizontal loops. In some applications, water is piped
from the ground or lake directly to the water source heat
pump. Piping is limited to the amount of pipe required to
get the water from the source to the unit.
NOTE: When utilizing Aquazone water source heat pumps
in ground loop systems, refer to design considerations in
the ground water system section.
Horizontal ground loop — This system is used when
adequate space is available and trenching can be easily ac-
complished. A series of parallel pipes are laid out in trench-
es 3 to 6 feet below the ground surface, and then back-
filled. Often, multiple pipes are used to maximize the heat
transfer capability of each trench. The amount of pipe and
the size of the ground loop field are based on ground
conditions, heating, and cooling requirements of the appli-
cation and system design.
50 SERIES
TYPE
SIZE (tons)
APPLICATION
50HQP,VQP Large Capacity
6-10 (HQP)
6
1
/
2
-25 (VQP)
Environmentally sound unit with Puron
®
refrigerant (R-410A) designed to handle
large zoned areas for all geothermal and
boiler/tower applications.
50PC Compact
1
1
/
4
-5
Compact WSHP with Puron refrigerant
(R-410A) for boiler/tower, ground water, or
ground loop systems.
50PS Premium
Efficiency
1
/
2
-6
Premium, ultra efficient unit with Puron
refrigerant (R-410A) for new boiler/tower,
ground water, or ground loop systems
50PEC High Efficiency
Console
3
/
4
-1
1
/
2
Efficient console unit with Puron refrigerant
(R-410A) and attractive design for finished
interior, under-window installations.
50PT Premium
Efficiency
2-6
Premium, ultra efficient 2-stage unit with
Puron refrigerant (R-410A) for new boiler/
tower, ground water, or ground loop
systems
50PSW Water-to-Water
3-28
Efficient unit with Puron refrigerant
(R-410A) serves as an alternative to pre-
heat or cool air. Unit can be used as a
stand-alone or supplemental boiler/chiller
in most hydronic heating applications. Also
conditions process fluids, lubricants, and
refrigerants.
50RTG Rooftop
3-20
Economical solution for indoor air quality
(IAQ) problems and tempering ventilation
air.
50VS Premium Effi-
ciency Vertical
Stack Heat Pump
3
/
4
to 3 Tons
Ultra efficient unit with environmentally
sound Puron refrigerant (R-410A) for
boiler/tower and geothermal applications
(condominiums, hotels, etc.). Stacked
design allows for common piping and sim-
plistic design.
Application data