Carrier 33ZCVAVTRM Specifications Page 109

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 108
21
dampers while the fan is operating. If local
heat is available, the series and parallel fans
shall start and local heat shall be enabled to
maintain its unoccupied heating set point. The
damper shall be modulated open to 70% after
heating is no longer required.
2. Cooling and Night Time Free Cooling (NTFC):
a. If the zone requirement is none, then the
zone controllers shall modulate their damp-
ers to maintain their minimum cooling
damper position or damper ventilation posi-
tion if the supply air temp is between 65 and
75 F. Any zone controllers servicing Series
terminals shall also modulate their dampers
to maintain their minimum cooling damper
position or damper ventilation position if the
supply air temp is between 65 and 75 F
after completing their SFTP cycle. During
the NTFC mode the zone controller shall
control between its heating and cooling set
points. During the other modes the zone
controller shall modulate its damper to its
occupied cooling set point.
b. If the zone requirement is cooling, then the
zone controllers shall modulate their air
dampers between their minimum and maxi-
mum cooling damper position to maintain
their cooling set point. Parallel fans shall be
disabled. Series fans shall start and control
after completing their SFTP cycle.
c. If the zone requirement is heating, then the
zone controllers shall modulate their damp-
ers to maintain their minimum cooling
damper position. Any zone controllers ser-
vicing Series fans shall complete their SFTP
cycle before modulating their dampers. Any
zone controllers servicing single duct units
with reheat capability shall maintain the
greater of either the minimum cooling
damper position or the minimum reheat
damper position. Zone controllers servicing
parallel units shall enable their fans. Zone
controllers servicing Series terminals shall
complete their SFTP cycle before modulat-
ing their dampers. After the fan starts, the
damper shall be modulated to maintain its
minimum cooling damper position.
3. Heat:
a. If the zone requirement is none, then the
zone controller shall maintain its minimum
heating damper position. Parallel fans shall
be disabled and their air damper shall be
modulated to maintain their minimum heat-
ing damper position. Series units shall com-
plete their SFTP cycle checks and then
modulate its damper to maintain its mini-
mum heating damper position.
b. If the zone requirement is cooling, then the
zone controller shall modulate its damper to
maintain its minimum heating damper posi-
tion. Parallel fans shall be disabled. Zone
controllers servicing Series units shall com-
plete their SFTP cycle and then shall modu-
late their primary damper to maintain their
minimum heating damper position.
4. Pressurization:
a. If the zone requirement is none or cooling,
then the zone controller shall maintain its
maximum cooling damper position. Parallel
fans shall be disabled. The damper for series
fans, after successfully completing its SFTP
cycle, shall modulate to maintain the maxi-
mum cooling damper position.
b. If the zone requirement is heating, and the
zone controller has been enabled to provide
local heating, then the zone controller shall
modulate its damper to its maximum cooling
damper position and enable its auxiliary
heat. If local heat is not available, the
damper shall be modulated to maintain its
maximum cooling damper position.
c. For series fan operations, the SFTP cycle
shall be completed before modulating the
primary air damper to its maximum cooling
damper position.
5. Evacuation:
During the Evacuation mode all terminal fans
shall be disabled and all dampers shall close.
Part 4 — Abnormal Conditions
4.01 The proposed system shall include the ability to
detect abnormal conditions, and to react to them
automatically.
A return to normal conditions shall also generate a
return to normal notification and the system shall
revert back to its original control scheme before the
abnormal condition existed.
The following abnormal terminal conditions shall
automatically generate an alarm and the system
shall take the following actions:
A. If a space temperature sensor is determined by the
zone controller to be invalid, the zone controller
shall generate an alarm, default to its Ventilation
mode and maintain its configured ventilation
damper position.
B. If a relative humidity sensor (monitor only function)
is determined by the zone controller to be invalid,
the zone controller shall generate an alarm.
C. If an indoor air quality sensor is determined by the
zone controller to be invalid, the zone controller
shall generate an alarm, and disable its IAQ
algorithm.
D. If a zone controller loses communication with its
associated coordinator, it shall generate an alarm. If
the zone controller does not have a supply-air sen-
sor installed, then the zone controller shall assume it
is in a Cooling mode and modulate its primary air
damper between its minimum and maximum
damper position. If the zone includes a reheat coil, it