The zone controller is a single duct, fan powered, Variable
Volume and Temperature (VVT®) terminal control with a
factory-integrated controller and actuator. The VVT zone con-
troller maintains precise temperature control in the space
by operating the terminal fan and regulating the flow of
conditioned air into the space. Buildings with diverse loading
conditions can be supported by controlling equipment heating
and cooling sources or supplemental heat.
The VVT zone controller (33ZCVVTZC-01) provides
dedicated control functions for single duct terminals with
modulating heat, up to 3 stages of ducted heat, or combination
baseboard and ducted heat. A relay board (33ZCOPTBRD-01)
is required for heat or fan terminals.
Carriers 3V™ control system provides optimized equip-
ment and component control through airside linkage. Linkage
refers to the process through which data is exchanged between
the air terminals and the air source that provides the supply air
to those terminals. The process “links” the terminals and the air
source to form a coordinated system. Linkage allows the air
source to operate efficiently and reliably while responding to
and satisfying changing conditions in the zones. Linkage also
allows the terminals to respond properly to changes in the air
source. A VVT zone controller configured as the Linkage
Coordinator manages the flow of data between the air source
and the VVT system zones.
Rooftop units, air handlers, fan coils, and water source heat
pumps feature product integrated or factory-installed controls
that are directly compatible with the 3V control system. The
rooftop units, air handlers, fan coils, and water source heat
pumps do not require any special hardware to be compatible
with the Carrier linkage system. Consult your local Carrier
representative for the complete list of compatible air source
controllers. Figure 1 shows an example of a Carrier linkage
system.
The VVT zone controllers are available factory-mounted to
Carriers round and rectangular dampers. Round dampers are
available in 6, 8, 10, 12, 14, and 16-in. sizes. Rectangular
dampers are available in 8x10, 8x14, 8x18, and 8x24-in. sizes.
All damper assemblies are equipped with an integrated duct
temperature sensor.
INSTALLATION
General —
The VVT zone controller is a microprocessor-
based direct digital control (DDC) controller that can be pur-
chased or installed on variable volume and temperature (VVT)
air terminals. It can be retrofitted on units manufactured by
Carrier or other manufacturers to provide pressure dependent
VVT control.
Each zone controller has the ability to function as a linkage
coordinator for systems with up to 32 zones. As a linkage
coordinator, a zone controller will retrieve and provide system
information to the rooftop or air-handling equipment and other
zone controllers. A zone controller can function as a stand
alone device by installing a duct air sensor.
The zone controller is connected to a wall-mounted, field-
supplied, space temperature sensor (SPT) in order to monitor
zone temperature changes and satisfy zone demand.
On stand-alone applications or applications with ducted or
modulating heat, the zone controller must be connected to a
field-supplied supply air temperature (SAT) sensor to monitor
the temperature of the air delivered by the air terminal. A
System Pilot can be used to adjust set points, set operating
parameters, and fully configure the zone controller or any
device on the system. A System Pilot can also provide local
space temperature, set point adjust, time broadcast, and sched-
ule adjustment for a single dedicated or remote device.
Carriers network software can be connected to the system
at the SPT sensor if Carrier network communication wiring is
run to the SPT sensor. The network software can be used to
adjust set points, set operating parameters, and fully configure
the zone controller or any device on the system.
Zone Controller Hardware — The zone controller
consists of the following hardware:
terminal control module
torque-limiting integrated damper actuator
plastic enclosure
•oneno.8x
1
/
2
-in. self-drilling sheet metal screw (to pre-
vent zone controller rotation)
Figure 2 shows the zone controller physical details.
Field-Supplied Hardware — Each zone controller re-
quires the following field-supplied components to complete its
installation:
air terminal unit (unless factory installed when pur-
chased as factory-installed option an SAT [supply-air
temperature] sensor is provided upstream of the damper
blade)
round or rectangular mounting bracket (for retrofit
applications)
space temperature sensor
transformer — 24 vac, 40 va
two no. 10 x
1
/
2
-in. sheet metal screws (to secure SAT
sensor to duct, if required)
two no. 6-32 x
5
/
8
-in. screws (to mount SPT [space tem-
perature] sensor base to electrical box)
contactors (if required for fan or electric heat)
supply air temperature sensor (required for terminal with
ducted heat)
option board 33ZCOPTBRD-01 (required for auxiliary
heat or fan terminals)
indoor air quality sensor (if required)
relative humidity sensor (if required)
one SPST (single pole, single throw) relay
valve and actuator for hot water heat (if required)
•wire
bushings (required when mounting SAT sensor in a duct
6-in. or less in diameter)
primary air temperature sensor (if required)
SPACE TEMPERATURE SENSOR — Each zone control-
ler requires a field-supplied Carrier space temperature sensor.
There are three sensors available for this application:
33ZCT55SPT, Space Temperature Sensor with Override
Button
33ZCT56SPT, Space Temperature Sensor with Override
Button and Set Point Adjustment
33PILOT-01, System Pilot Space Temperature Sensor,
User Interface, and Configuration Device
The System Pilot is a user interface to the Zone Controller
with a full complement of zone display features that can be
used to configure and operate the Zone Controller. It has an
SPT sensor and can transmit its value to the Zone Controller.
The System Pilot communicates to the Zone Controller
through the Zone Controllers dedicated Comm2 port or over
the main communication bus through Comm1.
OPTION BOARD The option board (33ZCOPTBRD-01)
is required for use of auxiliary heat and fan control functions.
The Option Board is field installed and provides four triac
discrete outputs, three for supplemental heat and one for the fan
output.
PRIMARY AIR TEMPERATURE SENSOR — A field-
supplied, primary air temperature (PAT) sensor (part number
33ZCSENPAT) is used on a zone controller which is function-
ing as a Linkage Coordinator for a non Carrier Network/
Linkage compatible air source.