MAX COOL DEMAND This variable displays the maxi-
mum cooling demand of all occupied linked zones, taking into
consideration the size of each zone as configured in the
Terminal Service Configuration Table. This is so that the size
of the zone will be considered when comparing its demand to
other zones.
Max Cool
Demand: Display Range delta 0.00 to 99.9 F
Network Access Read Only
MAX COOL DEMAND ZONE — This variable displays
the number of the zone that has the weighted maximum
cooling demand of all occupied linked zones. If all zones are
unoccupied then all zones will be included in the calculation.
Max Cool
Demand Zone: Display Range 0 to 31
Network Access Read Only
COOLING TIME GUARD — This variable displays the re-
maining time that the cooling mode must be active before a
mode change can take effect. The cooling time guard
timer becomes active whenever the COOL mode goes into
effect. This timer value is configured in the Master Service
Configuration Table.
Cooling
Time Guard: Display Range 0 to 255 minutes
Network Access Read Only
TIME GUARD OVERRIDE — This variable displays whether
there is a time guard override in effect. The override acts as a
one time override of any time guard in effect, heating or
cooling.
NOTE: The time guard override applies to the mode sent to the
air source. This is independent of the mode reselect function.
Forcing this point to Yes will allow the user to initiate a Time
Guard Override.
Time Guard
Override: Display Range Yes/No
Network Access Read/Write
HEAT MODE LOCK OUT — This variable displays whether
the system has been locked out of heating mode. If this
decision is forced to Yes, the system may not go into heating
mode regardless of how many zones are calling for heating.
Heat Mode
Lock Out: Display Range Yes/No
Network Access Read/Write
AVERAGE HEAT DEMAND — This variable displays the
average heating demand of all occupied linked zones, taking
into consideration the size of each zone as configured in the
Terminal Service Configuration Table. This is so that the size
of a zone will be considered when comparing its demand to
other zones. If all zones are unoccupied then all zones will be
included in the calculation.
Average Heat
Demand: Display Range delta 0.00 to 99.9 F
Network Access Read Only
MAX HEAT DEMAND This variable displays the maxi-
mum heating demand of all occupied linked zones, taking
into consideration the size of each zone as configured in the
Terminal Service Configuration Table. This is so that the size
of the zone will be considered when comparing its demand to
other zones.
Max Heat
Demand: Display Range delta 0.00 to 99.9 F
Network Access Read Only
MAX HEAT DEMAND ZONE This variable displays the
number of the zone that has the weighted maximum heating
demand of all occupied linked zones. If all zones are unoccu-
pied then all zones will be included in the calculation.
Max Heat
Demand Zone: Display Range 0 to 31
Network Access Read Only
HEATING TIME GUARD — This variable displays the re-
maining time that the heating mode must be active before a
mode change can take effect. The heating time guard timer be-
comes active whenever the HEAT mode goes into effect. This
timer value is configured in the Master Service Configuration
Table.
Heating
Time Guard: Display Range 0 to 255 minutes
Network Access Read Only
MODE RESELECT TIME This variable displays the re-
maining time that must elapse before the mode change can take
effect. The user can override the timer by forcing this
value. This timer value is configured in the Master Service
Configuration Table.
Mode Reselect
Time: Display Range 0 to 255 minutes
Network Access Read/Write
OUTDOOR AIR TEMPERATURE — This variable displays
the outdoor air temperature.
Outdoor Air
Temperature: Display Range –40 to 245 F
Network Access Read Only
Time Schedule Maintenance Table — The Time
Schedule Maintenance Table (OCCDEFME) displays occu-
pancy set points, the occupied mode and whether and override
is in progress. See Table 18.
MODE This variable displays the current occupied mode
for the zone controller. If the zone controller is following its
own local schedule, this is the result of the local schedule
status.
NOTE: This information only applies to the locally configured
occupancy schedule or if the zone controller is configured to
be the Global Schedule Master. The information does not
apply to a zone if it is following a global schedule.
Mode: Display Range 0 or 1 (1 = occupied)
Network Access None
CURRENT OCCUPIED PERIOD — If the zone controller
is configured to determine occupancy locally, this variable will
display the current period determining occupancy.
Current Occupied
Period: Display Range 1 to 8
Network Access None
OVERRIDE IN PROGRESS If an occupancy override is
in progress, this variable will display a yes.
Override In
Progress: Display Range Yes/No
Network Access None
OVERRIDE DURATION This variable displays the num-
ber of minutes remaining for an occupancy override which is in
effect. If the number of override hours was downloaded, the
value will be converted to minutes.
Override
Duration: Display Units minutes
Display Range 0 to 240
Network Access None
OCCUPIED START TIME This variable displays the
time that the current occupied mode began.
Occupied Start
Time: Display Range 00:00 to 23:59
Network Access None