Table 13 Linkage Maintenance Screen
Start Bias Time
This variable displays the Start Bias Time,
in minutes, calculated by the air source. The Start Bias Time is
calculated to bring the temperature up or down to the set point
under the optimum start routine. This value will be sent to all
associated zones for optimum start of zone controllers. This
function is supported by all Carrier equipment which perform
linkage.
Start Bias Time: Display Units minutes
Display range 0 to 185
Default Value 0
Network Access None
Average Occupied Heat Set Point
This variable displays
the weighted average of the occupied heat set point, calculated
by the linkage coordinator, from the information received from
polling its associated zones. The set points are weighted by the
maximum airflow capacities of the zone controllers scanned by
the linkage coordinator.
Average Occupied
Heat Set Point: Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access None
Average Occupied Cool Set Point
This variable displays
the weighted average of the occupied cool set point, calculated
by the linkage coordinator, from the information received from
polling its associated zones. The set points are weighted by the
maximum airflow capacities of the zone controllers scanned by
the linkage coordinator.
Average Occupied
Cool Set Point: Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access None
Average Unoccupied Heat Set Point
This variable displays
the weighted average of the unoccupied heat set point, calculat-
ed by the linkage coordinator, from the information received
from polling its associated zones. The set points are weighted
by the maximum airflow capacities of the zone controllers
scanned by the linkage coordinator.
Average Unoccupied
Heat Set Point: Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access None
Average Unoccupied Cool Set Point
This variable dis-
plays the weighted average of the unoccupied cool set point,
calculated by the linkage coordinator, from the information re-
ceived from polling its associated zones. The set points are
weighted by the maximum airflow capacities of the zone con-
trollers scanned by the linkage coordinator.
Average Occupied
Cool Set Point: Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access None
Average Zone Temperature
This variable displays the
weighted average of the space temperatures, collected by the
linkage coordinator, from polling its associated zones. The
temperatures are weighted by the maximum airflow capacities
of the zone controllers scanned by the linkage coordinator.
Average Zone
Temperature: Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access Read Only
Average Occupied Zone Temperature
This variable dis-
plays the weighted average of the space temperatures of occu-
pied zones, collected by the linkage coordinator, from polling
its associated zones. The temperatures are weighted by the
maximum airflow capacities of the zone controllers scanned by
the linkage coordinator.
Average Occupied
Zone Temperature:Display Units F (C)
Display Range 0.0 to 99.9
Default Value 0.0
Network Access Read Only
DESCRIPTION DEFAULT POINT NAME
Air Source Bus Number
0 ASBUSNUM
Air Source Element Number
0 ASDEVADR
Master Zone Element Number
0MZDEVADR
Operating Mode
OFF ASOPMODE
Air Source Supply Temperature
0 F ASTEMP
Start Bias Time
0 minutes STRTBIAS
Average Occupied Heat Set Point
0.0 F AOHS
Average Occupied Cool Set Point
0.0 F AOCS
Average Unoccupied Heat Set Point
0.0 F AUHS
Average Unoccupied Cool Set Point
0.0 F AUCS
Average Zone Temperature
0.0 F AZT
Average Occupied Zone Temperature
0.0 F AOZT
Composite CCN Value
0 CCCNVAL
Occupancy Status
0 OCCSTAT
Next Occupied Day
(blank) NXTOCCD
Next Occupied Time
00:00 NXTOCCT
Next Unoccupied Day
(blank) NXTUNOD
Next Unoccupied Time
00:00 NXTUNOT
Previous Unoccupied Day
(blank) PREVUNOD
Previous Unoccupied Time
00:00 PRVUNOT
Maximum Damper Position
0.0 % MAXDMPOS
Static Pressure Reset
0.0 in. wg PRESVAL
Pressure Decrease Value
0.000 in. wg PRESDECR
Pressure Increase Value
0.000 in. wg PRESINCR
801