42
Table 16 Linkage Maintenance Table
REF ZONE TEMPERATURE This variable displays the
weighted average of the space temperatures, collected by the
linkage coordinator, from polling its associated zones. The
temperatures are weighted by the maximum airflow capacities
of the zone controllers scanned by the linkage coordinator.
Ref Zone
Temperature: Display Units F (C)
Display Range –40.0 to 245.0
Network Access Read Only
OCCUPIED REF ZONE TEMPERATURE — This variable
displays the weighted average of the space temperatures of
occupied zones, collected by the linkage coordinator, from
polling its associated zones. The temperatures are weighted by
the maximum airflow capacities of the zone controllers
scanned by the linkage coordinator.
Occupied Ref
Zone Temperature:Display Units F (C)
Display Range –40.0 to 245.0
Network Access Read Only
COMPOSITE CCN VALUE This variable displays the
high, low or average of the CCN variable collected from each
zone as configured in the Linkage Master (Coordinator) Con-
figuration Screen. The value is sent to the network address and
variable specified within that configuration table.
Composite
CCN Value: Display Range 0 to 65535
Network Access Read Only
OCCUPANCY STATUS This variable displays a “1”
when at least one of the associated zone controllers (that are
being scanned) is in the occupied mode.
Occupancy Status:Display Range 0 or 1 (1 = occupied)
Network Access Read only
NEXT OCCUPIED DAY This variable displays the day
when the next associated zone is scheduled to change from
unoccupied to occupied mode. This point is read in conjunction
with the next occupied time to allow the user to know the next
time and day when a zone will become occupied.
Next Occupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
NEXT OCCUPIED TIME This variable displays the time
of day when the next associated zone is scheduled to change
from unoccupied to occupied mode. This point is read in con-
junction with the next occupied day to allow the user to know
the next time and day when a zone will become occupied.
Next Occupied
Time: Display Range 00:00 to 24:00
Network Access None
NEXT UNOCCUPIED DAY — This variable displays the
day when the next associated zone is scheduled to change from
occupied to unoccupied mode. This point is read in conjunction
with the next unoccupied time to allow the user to know the
next time and day when a zone will become unoccupied.
Next Unoccupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
NEXT UNOCCUPIED TIME — This variable displays the
time of day when the next associated zone is scheduled to change
from occupied to unoccupied mode. This point is read in con-
junction with the next unoccupied day to allow the user to know
the next time and day when a zone will become unoccupied.
Next Unoccupied
Time: Display Range 00:00 to 24:00
Network Access None
PREVIOUS UNOCCUPIED DAY — This variable displays
the day when the last associated zone changed from occupied
to unoccupied mode. This point is read in conjunction with the
previous unoccupied time to allow the user to know the last
time and day when a zone became unoccupied.
Previous Unoccupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
PREVIOUS UNOCCUPIED TIME — This variable displays
the time of day when the last associated zone changed from
occupied to unoccupied mode. This point is read in conjunction
with the previous unoccupied day to allow the user to know the
last time and day when a zone became unoccupied.
Previous Unoccupied
Time: Display Range 00:00 to 24:00
Network Access None
DESCRIPTION VALUE UNITS STATUS FORCE NAME
Zone Linkage
Air Source Bus # 0 ASBUSNUM
Air Source Element # 8 ASDEVADR
Master Zone Element # 118 MZDEVADR
Operating Mode COOLING ASOPMODE
Air Source Supply Temp 55.0 dF ASTEMP
Start Bias Time 0 min STRTBIAS
Occ Heat Setpt 68.0 dF OHS
Occ Cool Setpt 74.0 dF OCS
Unoc Heat Setpt 64.0 dF UHS
Unoc Cool Setpt 78.0 dF UCS
Ref Zone Temp 71.0 dF ZT
Occ Ref Zone Temp 71.0 dF OZT
Composite CCN Value 0.0 CCCNVAL
OccupancyStatus(1=occ) 0 OCCSTAT
Next Occupied Day Fri NXTOCCD
Next Occupied Time 10:15 NXTOCCT
Next Unoccupied Day NXTUNOD
Next Unoccupied Time 00:00 NXTUNOT
Prev Unoccupied Day Fri PRVUNOD
Prev Unoccupied Time 04:01 PRVUNOT
Page view 69
1 2 ... 65 66 67 68 69 70 71 72 73 74 75 ... 315 316