Table 20 — Occupancy Maintenance Screen
(OCCPC63S-64S)
Primary Maintenance Screen — The primary
Maintenance Screen (MAINT) is used to service the Premier-
Link™ controller. See Table 21.
THERMOSTAT CONTROL Indicates the result of the
configuration decision to control in the thermostat or sensor
mode.
Thermostat
Control: Display Range: No/Yes
Default Value: Yes
Network Access: Read Only
OCCUPIED The Occupied point indicates whether or not
the controller is operating in the Occupied mode.
Occupied: Display Range No/Yes
Default Value No
Network Access Read/Write
OVERRIDE TIME REMAINING — If the controller is a
global schedule follower and Global Override Enable is set to
No, then this point becomes the override timer.
Override Time
Remaining: Display Units Minutes
Display Range 0 to 240
Default Value 0
TIMED OVERRIDE IN EFFECT — The Timed Override In
Effect point shows if a timed override is currently in effect.
NOTE: For controllers using a global schedule, Global Over-
ride Enable must be set to NO on all controllers configured for
global schedule, including the global schedule broadcaster, for
individual override to be enabled.
Timed Override
in Effect: Display Range No/Yes
Default Value No
Network Access Read Only
START BIAS TIME The Start Bias Time, in minutes, is
calculated during the unoccupied period by the controller as
needed to bring the temperature up or down to the set point un-
der the optimum start routine. The start time bias for heat and
cool are configurable. This value will be reported to the Link-
age Thermostat if it is used. It cannot be used with Global
Scheduling.
Start Bias Time: Display Units minutes
Display Range 0 to 180
Default Value 0
Network Access Read only
HEAT The Heat point shows if there is a demand for heat in
the space. The space temperature must be below the Occupied
Low or Unoccupied Low set point.
NOTE: When a control mode ends, “NO” mode must be com-
pleted before opposite mode can begin.
Heat: Display Range No/Yes
Default Value No
Network Access None
COOL The Cool point shows if there is a demand for cool-
ing in the space. The space temperature must be above the Oc-
cupied High or Unoccupied High set point.
NOTE: When a control mode ends, “NO” mode must be com-
pleted before opposite mode can begin.
Cool: Display Range No/Yes
Default Value No
Network Access None
IAQ CONTROL The IAQ control indicates whether or not
IAQ control is active in the controller. IAQ control of the mini-
mum damper position is active whenever the configured
parameters for the IAQ PID calculate a minimum position
greater than the configured economizer minimum position.
IAQ Control: Display Range: No/Yes
Default Value: No
Network Access: Read Only
DEMAND LIMIT Demand limit indicates that a com-
mand has been received to limit capacity or reduce capacity of
the heating or cooling.
Demand Limit: Display Range: No/Yes
Default value: No
Network Access: Read Only
TEMP COMPENSATED START — The temperature com-
pensated start function indicates that the controller has started
the equipment prior to occupancy in order to be at the occupied
set points at the start of occupancy.
Temp
Compensated
Start: Display Range: No/Yes
Default Value: No
Network Access: Read Only
IAQ PRE-OCCUPANCY PURGE — The IAQ pre-
occupancy purge indicates that the pre-occupancy purge
mode is currently active.
IAQ
Pre-occupancy
Purge: Display Range: No/Yes
Default Value: No
Network Access: Read Only
UNOCCUPIED FREE COOLING The unoccupied free
cooling point indicates that unoccupied free cooling is in effect.
Unoccupied Free
Cooling: Display Range: No/Yes
Default Value: No
Network Access: Read Only
FIRE SHUTDOWN The fire shutdown point indicates in a
sensor mode that the Fire shutdown input has been sensed. This
will cause the supply fan and heating and cooling to be turned
off also.
Fire Shutdown: Display Range: No/Yes
Default Value: No
Network Access: Read/Write
LINKAGE CONTROL Linkage control indicates if the
controller is receiving linkage communication.
Linkage Control: Display Range: No/Yes
Default Value: No
Network Access: Read/Write
FIELD/STARTUP TEST — This point is used to enable field
test of the controller. When forced to Yes, the controller will
DESCRIPTION VALUE UNITS NAME
Mode 0 MODE
Current Occupied Period 0 PERIOD
Override in Progress No OVERLAST
Override Duration 0 min OVERDURA
Occupied Start Time 00:00 OCCSTART
Unoccupied Start Time 00:00 UNSTART
Next Occupied Day NXTOCCD
Next Occupied Time 00:00 NXTOCCT
Next Unoccupied Day NXTUNOD
Next Unoccupied Time 00:00 NXTUNOT
Last Unoccupied Day PRVUNOD
Last Unoccupied Time 00:00 PRVUNOT