Carrier 33ZCVAVTRM Specifications Page 144

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 143
18
Enthalpy Switch/Receiver — The accessory en-
thalpy switch/receiver (33CSENTHSW) senses temperature
and humidity of the air surrounding the device and calculates
the enthalpy when used without an enthalpy sensor. The relay is
energized when enthalpy is high and deenergized when en-
thalpy is low (based on ASHRAE [American Society of Heat-
ing, Refrigeration, and Air Conditioning Engineers] 90.1 crite-
ria). If an accessory enthalpy sensor (33CSENTSEN) is at-
tached to the return air sensor input, then differential enthalpy is
calculated. The relay is energized when the enthalpy detected by
the return air enthalpy sensor is less than the enthalpy at the en-
thalpy switch/receiver. The relay is deenergized when the en-
thalpy detected by the return air enthalpy sensor is greater than
the enthalpy at the enthalpy switch/receiver (differential en-
thalpy control). See Fig. 22 and 23.
OUTDOOR ENTHALPY CONTROL (Fig. 24) — Outdoor
enthalpy control requires only an enthalpy switch/receiver
(33CSENTHSW). The enthalpy switch/receiver is mounted in
the outdoor air inlet and calculates outdoor air enthalpy. The
enthalpy switch/receiver energizes the relay output when the
outdoor enthalpy is above 28 BTU/lb OR dry bulb tempera-
ture is above 75 F and is deenergized when the outdoor
enthalpy is below 27 BTU/lb AND dry bulb temperature is
below 74.5 F. The relay output is wired to the unit economizer
which will open or close depending on the output of the
switch.
NOTE: The enthalpy calculation is done using an average alti-
tude of 1000 ft above sea level.
Mounting
— Mount the enthalpy switch/receiver in a location
where the outdoor air can be sampled (such as the outdoor air
intake). The enthalpy switch/receiver is not a NEMA 4 enclo-
sure and should be mounted in a location that is not exposed to
outdoor elements such as rain or snow. Use two field-supplied
no. 8 x
3
/
4
-in. TEK screws. Insert the screws through the holes
in the sides of the enthalpy switch/receiver.
Wiring
— Carrier recommends the use of 18 to 22 AWG
twisted pair or shielded cable for all wiring. All connections
must be made with
1
/
4
-in. female spade connectors.
A 24-vac transformer is required to power the enthalpy
switch/receiver; as shown in Fig. 24, the PremierLink™ board
provides 24 vac. Connect the GND and 24-vac terminals on the
enthalpy switch/receiver to the terminals on the transformer.
On some applications, the power from the economizer harness
can be used to power the enthalpy switch/receiver. To power
the enthalpy switch/receiver from the economizer harness, con-
nect power of the enthalpy switch/receiver to the red and
brown wires (1 and 4) on the economizer harness.
For connection to rooftop units with PremierLink™ control,
connect the LOW Enthalpy terminal on the enthalpy switch/re-
ceiver to J4 — pin 2 of the PremierLink control on the HVAC
(Heating, Ventilation, and Air Conditioning) unit. The switch
can be powered through the PremierLink control board if de-
sired. Wire the 24-vac terminal on the enthalpy switch/receiver
to J4 — pin 1 on the PremierLink control. Wire the GND ter-
minal on the enthalpy switch/receiver to J1 — pin 2 on the Pre-
mierLink control. The HI Enthalpy terminal is not used. See
Fig. 24.
DIFFERENTIAL ENTHALPY CONTROL (Fig. 25) —
Differential enthalpy control requires both an enthalpy switch/
receiver (33CSENTHSW) and an enthalpy sensor
(33CSENTSEN). The enthalpy switch/receiver is mounted in
the outdoor air inlet and calculates outdoor air enthalpy. The
enthalpy sensor is mounted in the return airstream and calcu-
lates the enthalpy of the indoor air.
The enthalpy switch/receiver energizes the HI Enthalpy re-
lay output when the outdoor enthalpy is greater than the indoor
enthalpy. The LOW Enthalpy terminal is energized when the
outdoor enthalpy is lower than the indoor enthalpy. The relay
output is wired to the unit economizer which will open or close
depending on the output of the switch.
NOTE: The enthalpy calculation is done using an average alti-
tude of 1000 ft above sea level.
Mounting
— Mount the enthalpy switch/receiver in a location
where the outdoor air can be sampled (such as the outdoor air
intake). The enthalpy switch/receiver is not a NEMA 4 enclo-
sure and should be mounted in a location that is not exposed to
outdoor elements such as rain, snow, or direct sunlight. Use
two field-supplied no. 8 x
3
/
4
-in. TEK screws. Insert the screws
through the holes in the sides of the enthalpy switch/receiver.
Fig. 22 — Enthalpy Switch/Receiver Dimensions
Fig. 23 — Enthalpy Sensor Dimensions
(33CSENTSEN)
Page view 143
1 2 ... 139 140 141 142 143 144 145 146 147 148 149 ... 315 316

Comments to this Manuals

No comments