Carrier 33ZCVAVTRM Specifications Page 236

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 235
38
Inverse Loop Polarity
If the output responds in reverse of what is expected, reverse
the polarity of the submaster gain (+/-). An example of this
condition is when the reference requires heat, but the valve
goes closed or moves towards closed. After the required
corrections are made, re-evaluate for the other possible
conditions.
3. Set the Master Integral Gain to 0.
4. Adjust the Master Proportional Gain.
At this point, the submaster loop is stable and its gain has
been adjusted for proper response. Adjust the setpoint to a
value +/- 5% away from current conditions at the controlling
sensor (normally the space sensor) and remove the submaster
force to allow the master loop to calculate a new submaster
reference (based on the amount of error between the master
sensor and the setpoint). This will allow the equipment to
operate with a legitimate load. Observe the loop response and
determine if the following condition is present:
Loop Oscillation.
If the submaster reference swings wildly from its maxi-
mum to its minimum allowable value, the most likely
cause is an excessive amount of master proportional gain.
Reduce the master proportional gain in increments of
50% until stability results, then increase its value by half
of the reduced amount. Since the master loop in this
example runs every two minutes, you are advised to allow
a minimum of eight minutes (four loop iterations) be-
tween successive gain adjustments. The intent is to
produce a steady output signal without reaching the
minimum and maximum submaster values. At this point
the loop should stabilize at an output that will likely not
achieve setpoint. This is normal, and we will compensate
for this by adjustment of the integral gain.
5. Set the Integral Gain.
Once the proportional gain is established, input a value of
integral gain that is between 10% and 50% of the proportional
Page view 235
1 2 ... 231 232 233 234 235 236 237 238 239 240 241 ... 315 316

Comments to this Manuals

No comments