Carrier 33ZCVAVTRM Specifications Page 164

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 163
38
SAT CMP2 LOCKOUT TEMP — The SAT CMP2 Lockout
Temperature displays the low supply temperature set point for
compressor no. 2 supply air during cooling. If compressor no. 2
is on during Cooling mode, the economizer will assist the cool-
ing and work to maintain a discharge-air temperature slightly
above lockout temperature set point. If the economizer is at
minimum and the supply-air temperature goes below Lockout
Temperature set point, the compressor will cycle to maintain
the supply air set point. The minimum on and off times and
stage-up and down timers will still be in effect.
SAT CMP2
Lockout Temp: Units degrees F (degrees C)
Range 45.0 to 55.0
Default Value 50.0
STAGED COOLING The staging function is used for DX
cooling (1 or 2 stages). The staging function uses the cooling
submaster reference from the PID and compares the value to
the supply-air temperature to calculate the required number of
output stages to energize.
Time Guard delays are provided to allow for up to 2 stages
of compression. Also, a DX Lockout will prevent operation
of the DX cooling if the outdoor air temperature is below this
value.
The cooling algorithm controls the valve or stages of DX
cooling to prevent the space temperature from exceeding the
current cooling set point (which includes any calculated offset
value from a T56 sensor slide bar or T59 sensor during occu-
pied periods). Also, the cooling is controlled so that the supply
air temperature does not fall below 50 F when cooling is active.
Number of Stages: Range 1 to 3
Default Value 2
The Time Guards must be set to Enable for output to a
compressor, and set to Disable for output to a valve or
compressor unloader.
When enabled, the staging PID loop will have a minimum
delay of 3 minutes before adding the stage and dropping the
stage after it is started. This delay will run concurrently with
the Compressor Minimum On (C_MIN_ON) and Off
(C_MIN_OF) delays found in this table. The actual compres-
sor on/off delays will be the greater of the two functions.
When disabled, there will be no delay in adding or droping the
stage other then the Compressor Minimum On and Off Delays.
NOTE: Stage 1 Time Guard cannot be disabled.
Stage 1
Time Guard: Range Disable/Enable
Default Value Enable
Stage 2
Time Guard: Range Disable/Enable
Default Value Enable
Stage 3 (not used)
Time Guard: Range Disable/Enable
Default Value Disable
HEATING PID The PremierLink™ controller determines
if a heating demand exists in the space. The controller reads the
space temperature sensor and compares the temperature to the
current low set point (including any calculated offset value
from a T56 or T59 sensor) during occupied periods. If it is
below the set point, and heating is configured and available, it
then calculates the required supply-air temperature to satisfy
the given conditions. The calculated value (heating submaster
reference) is compared to the actual supply-air temperature and
the output is then adjusted to satisfy conditions by using a
Proportional/Integral/Derivative (PID) loop.
The Heating PID includes the following set points: Propor-
tional Gain, Integral Gain, Derivative Gain, and Starting Value.
Proportional Gain: Range –100.0 to 100.0
Default Value 6.0
Integral Gain: Range –5.0 to 5.0
Default Value 3.0
Derivative Gain: Range –20.0 to 20.0
Default Value 5.0
Starting Value: Units degrees F (degrees C)
Range 40.0 to 120.0
Default Value 75.0
NOTE: If configured for heat pump operation, the propor-
tional, integral, and derivative gains need to be changed to the
following values: proportional gain - 10.0, integral gain - 1.0 to
2.0, derivative gain - 3.0.
SAT HIGH SET POINT This is the maximum duct tem-
perature value that will be calculated by heating algorithm dur-
ing the heat mode.
SAT High
Setpoint: Display Unit degrees F (degrees C)
Range 100.0 to 140.0 F
Default Value 140.0 F
STAGED HEATINGThe Staged Heating function is used
for two-position valves or for electric heat (1 or 2 stages). The
staging function uses the heating submaster reference value
from the PID and compares it to the supply-air temperature to
calculate the required number of output stages to energize. The
time guard, when enabled, will increase the heat output mini-
mum off time from 3 minutes to 5 minutes.
Number of Stages: Range 1 to 3
Default Value 2
Stage 1
Time Guard: Range Disable/Enable
Default Value Enable
Stage 2
Time Guard: Range Disable/Enable
Default Value Enable
Stage 3
Time Guard: Range Disable/Enable
Default Value Enable
IAQ PID The proportional gain affects the response of PID
calculations for staged control. The gain is also used for two
position control to establish the hysteresis between on and off.
A larger gain speeds response time or reduces the hysteresis,
while a smaller gain requires a larger error to generate the same
response to changes in Indoor Air Quality. Enter the desired
proportional gain for the Indoor Air Quality control algorithm.
The integral gain affects the PID calculation; an increase
will make the IAQ submaster reference change greater as the
error in indoor air quality increases. The integral gain should be
selected to eliminate proportional droop without overshoot.
Enter the desired integral gain for the Indoor Air Quality con-
trol algorithm.
The Derivative Gain is typically not required for Indoor Air
Quality operation and should be left at the default value.
The Starting Value is used to establish the starting value for
the IAQ PID calculation.
Page view 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 315 316

Comments to this Manuals

No comments