Composite CCN Value
This variable displays the high, low
or average of the CCN variable collected from each zone as
configured in the Linkage Coordinator Configuration Screen.
The value is sent to the CCN address and variable specified
within that configuration table.
Composite
CCN Value: Display Range 0-65535
Default Value 0
Network Access Read Only
Occupancy Status
This variable displays a 1 when at
least one of the associated zone controllers (that are being
scanned) is in the occupied mode.
Occupancy Status:Display Range 0 or 1 (1 = occupied)
Default Value 0
Network Access Read only
Next Occupied Day
This variable displays the day when
the next associated zone is scheduled to change from unoccu-
pied to occupied mode. This point is read in conjunction with
the next occupied time to allow the user to know the next time
and day when a zone will become occupied.
Next Occupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value No display (Blank)
Network Access None
Next Occupied Time
This variable displays the time of day
when the next associated zone is scheduled to change from un-
occupied to occupied mode. This point is read in conjunction
with the next occupied day to allow the user to know the next
time and day when a zone will become occupied.
Next Occupied
Time: Display Range 00:00 to 24:00
Default Value 0:00
Network Access None
Next Unoccupied Day
This variable displays the day when
the next associated zone is scheduled to change from occupied
to unoccupied mode. This point is read in conjunction with the
next unoccupied time to allow the user to know the next time
and day when a zone will become unoccupied.
Next Unoccupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value No display (Blank)
Network Access None
Next Unoccupied Time
This variable displays the time of
day when the next associated zone is scheduled to change from
occupied to unoccupied mode. This point is read in conjunction
with the next unoccupied day to allow the user to know the
next time and day when a zone will become unoccupied.
Next Unoccupied
Time: Display Range 00:00 to 24:00
Default Value 0:00
Network Access None
Previous Unoccupied Day
This variable displays the day
when the last associated zone changed from occupied to unoc-
cupied mode. This point is read in conjunction with the previ-
ous unoccupied time to allow the user to know the last time and
day when a zone became unoccupied.
Previous Unoccupied
Day: Display Range MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value No display (Blank)
Network Access None
Previous Unoccupied Time
This variable displays the time
of day when the last associated zone changed from occupied to
unoccupied mode. This point is read in conjunction with the
previous unoccupied day to allow the user to know the last time
and day when a zone became unoccupied.
Previous Unoccupied
Time: Display Range 00:00 to 24:00
Default Value 0:00
Network Access None
Maximum Damper Position
This variable displays the
damper position of the zone controller in the system with the
damper in the most open position. This is used by the linkage
coordinator to calculate the static pressure reset.
Maximum Damper
Position: Display Units % (open)
Display Range 0.0 to 100.0
Default Value 0.0
Network Access Read/Write
Static Pressure Reset
This variable displays the current
static pressure reset calculated, using the maximum damper po-
sition and the configuration information from the linkage con-
figuration table.
Static Pressure
Reset: Display Units in. wg
Display Range 0.0 to 5.0
Default Value 0.0
Network Access Read/Write
Pressure Decrease Value
If the maximum damper position
in the system goes below the minimum configuration setting,
the linkage coordinator will calculate an amount that the static
pressure should be decreased. This is used to open the system
dampers more so that they will modulate between their mini-
mum and maximum settings.
This number is rounded to the nearest tenth of an inch and
will be added to the static pressure reset value unless the static
pressure reset value has reached maximum reset.
Pressure Decrease
Value: Display Units in. wg
Display Range 0.000 to 5.000
Default Value 0.000
Network Access Read/Write
Pressure Increase Value
If the maximum damper position
in the system goes above the maximum configuration setting,
the linkage coordinator will calculate an amount that the static
pressure should be increased. This is used to close the system
dampers more so that they will modulate between their mini-
mum and maximum settings.
This number is rounded to the nearest tenth of an inch and
will be subtracted to the static pressure reset value unless the
static pressure reset value has reached zero.
Pressure Increase
Value: Display Units in. wg
Display Range 0.000 to 5.000
Default Value 0.000
Network Access Read/Write
OCCUPANCY MAINTENANCE TABLE The Occu-
pancy Maintenance table is used to view the occupancy set
points. See Table 14.
Mode
This variable displays the current occupied mode for
the zone controller. If the zone controller is following its own
local schedule, this is the result of the local schedule status. If
the zone controller is configured to follow a global schedule,
this point displays the mode last received from a global sched-
ule broadcast.
Mode: Display Range 0 or 1 (1 = occupied)
Default Value 0
Network Access None
801