2
GENERAL
The PremierLink™ controller, version 2.0, is a field retrofit
rooftop control compatible with the Carrier Comfort Net-
work® (CCN) system. This control is designed to allow users
the access and ability to change factory-defined settings, thus
expanding the function of the standard unit control board. The
complete PremierLink package (part number 33CSPREMLK)
consists of a rooftop control circuit board with plastic cover
and label, wire harnesses, spade connectors, wire nuts and 4
mounting screws.
Access is available via an RJ-11 connection or a 3-wire con-
nection to the communication bus. User interfaces available for
use with the CCN system are PCs equipped with Carrier user
interface software such as Service Tool, ComfortVIEW™, or
ComfortWORKS® software. When used as part of the CCN
system, other devices such as the CCN data transfer, System
Pilot™, Touch Pilot™, or Comfort Controller can read data
from or write data to the PremierLink retrofit controller.
INSTALLATION
Inspection —
Inspect package contents for visual defects
that may have occurred during shipping. If there is any dam-
age, contact your local representative before proceeding.
PremierLink Controller Hardware — The Premier-
Link package consists of the following hardware:
control module (with plastic cover and label)
7 wire harnesses
10 spade connectors
wire nuts
4 no. 6x1-in. self-drilling Phillips pan head mounting
screws
Field-Supplied Hardware — The PremierLink con-
troller is configurable with the following field-supplied
sensors:
space temperature sensor (33ZCT55SPT, 33ZCT56SPT,
33ZCT58SPT, or 33ZCT59SPT) in sensor mode or thermo-
stat mode for economizer control
supply air temperature sensor (33ZCSENSAT) required for
all applications
indoor air quality sensor (33ZCSENCO2, 33ZCT55CO2,
33ZCT56CO2) required only for demand control
ventilation. A dedicated 24-vac transformer is required.
outdoor air quality sensor (33ZCTSENCO2) required only
for demand control ventilation
outdoor air temperature sensor (33ZCSENOAT)
outdoor air enthalpy switch (33CSENTHSW)
filter switch (third party differential airflow)
return air enthalpy sensor (33CSENTSEN)
• indoor relative humidity sensor (33ZCSENSRH-01),
required only for dehumidification
For specific details about sensors, refer to the literature
supplied with the sensor.
SPACE TEMPERATURE (SPT) SENSOR — A field-supplied
Carrier space temperature sensor is required to maintain space
temperature in sensor mode. There are four sensors available for
this application:
33ZCT55SPT, space temperature sensor with override
button
33ZCT56SPT, space temperature sensor with override
button and set point adjustment
33ZCT58SPT, T58 communicating room sensor with over-
ride button, set point adjustment, and manual fan control
33ZCT59SPT, space temperature sensor with LCD (liquid
crystal display) screen, override button, and set point
adjustment
If controlling an economizer in the thermostat mode, a duct
sensor must be mounted in the return air duct and wired to SPT
input.
SUPPLY AIR TEMPERATURE (SAT) SENSOR — The
PremierLink controller must be connected to a field-supplied
supply air temperature (SAT) sensor (part number
33ZCSENSAT) to monitor the temperature of the air delivered.
The SAT consists of a thermistor encased within a stainless
steel probe. The probe is 6 in. nominal length. The SAT sensor
has 114 in. of unshielded, plenum-rated cable (2 conductors,
22 AWG [American Wire Gage]). The sensor range is –40 to
185 F with a nominal resistance of 10,000 ohms at 77 F. The
sensor measures temperature with an accuracy of ±0.36 F.
Ideally, the SAT sensor should be located inside the unit
under the heat exchanger. The SAT sensor can also be installed
in the supply air duct downstream from unit heat source to
control.
INDOOR AIR QUALITY CO
2
SENSOR An indoor air
quality sensor is required for CO
2
level monitoring. Three
different CO
2
sensors are available for this application:
33ZCSENCO2 sensor is an indoor, wall-mounted sensor
with an LCD (liquid-crystal display) screen
33ZCT55CO2 sensor is an indoor, wall-mounted sensor
without display. The CO
2
sensor also includes a space tem-
perature sensor with override button
33ZCT56CO2 sensor is an indoor, wall-mounted sensor
without display. The CO
2
sensor also includes a space tem-
perature sensor with override button and temperature offset
OUTDOOR AIR QUALITY CO
2
SENSOR — The
outdoor air CO
2
sensor (33ZCSENCO2) is designed to moni-
tor carbon dioxide (CO
2
) levels found in diesel exhaust and
control ventilation systems. It comes with an outdoor enclo-
sure. This sensor provides an outdoor baseline for differential
DCV (Demand Control Ventilation) control.
NOTE: The relative humidity sensor and the outdoor air CO
2
sensor cannot both be used on the controller at the same time.
RELATIVE HUMIDITY SENSOR — The 33ZCSENSRH-
01 relative space humidity sensor is required for dehumidifica-
tion control on a rooftop unit equipped with a dehumidification
device. Otherwise, the relative humidity sensor is used for
monitoring only.
NOTE: The relative humidity sensor and the outdoor air CO
2
sensor cannot both be used on the controller at the same time.
OUTDOOR AIR TEMPERATURE SENSOR — The
outdoor air temperature sensor (33ZCSENOAT) monitors the
temperature of the outside air. If the sensor is to be installed in
the outdoor air duct instead of an outdoor location, sensor
33ZCSENPAT should be used.
OUTDOOR AIR ENTHALPY SWITCH/RECEIVER
(33CSENTHSW) This device measures both temperature
and humidity and converts the data into a relay output depen-
dent on the sensor mode. Mode 1 is designed to energize the
relay at a fixed set point of 28 Btu/lb or 75 F. Mode 2 is used in
conjunction with the Return Air Enthalpy Sensor
(33CSENTSEN) to measure both indoor and outdoor enthalpy
and to determine which is greater. The enthalpy switch output
can be normally open or normally closed.
FILTER SWITCH A field-supplied third-party differential
air flow switch with normally open contacts is requried for de-
tection of dirty filters. The switch must be rated for a minimum
of 5 va at 24 vac.
IMPORTANT: PremierLink part number 33CSPREMLK
should only be used in applications where the integrity
of the Underwriters Laboratories rating will be
maintained.