31
Table 6 — Terminal Service Configuration Table
DESCRIPTION VALUE UNITS NAME
COOLING
Terminal Type 1 TERMTYPE
1=SingleDuct
2=ParallelFan
3=SeriesFan
Primary Inlet Size
Inlet Diameter (Inches) 6.0 RNDSZ
Inlet Area (Sq. In.) 0.0 SQA
Damper PID
Proportional Gain 10.0 KP
Integral Gain 2.5 KI
Derivative Gain 4.0 KD
Starting Value 40.0 %STARTVAL
CW Rotation Close DMPDIR
HEATING
Heat Type 0 HEATTYPE
0=None
2 = Two Position
3 = Staged Electric
4 = Modulating/CV
5=Combination
Heating PID
Proportional 10.0 KP
Integral Gain 0.5 KI
Derivative Gain 0.0 KD
Starting Value 80.0 dF STARTVAL
Ducted Heat Yes DUCTHEAT
Maximum Temperature 110 dF MAXTEMP
# Electric Heat Stages 3 STAGES
Heat On Delay 2 min HONDEL
Fan Off Delay 2 min FNOFFD
2-Pos Heat Logic Normal HEATYPE
System Call for Heat? Yes HEATCALL
Supp. Heat Lockout Temp. 140.0 dF SHL_TEMP
System Pilot Averaging 0 SENS_AVG
0 = System Pilot only
1=withoneT55
2 = with four T55s
3 = with nine T55s
SPT Sensor Trim 0.0 ^F SPTTRIM
SAT Sensor Trim 0.0 ^F SATTRIM
Local SAT Installed Yes LOC_SAT
Remote Contact Config Close RMTCFG
1104