Carrier 33ZCVAVTRM Specifications Page 61

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 60
33
REMOTE CONTACT CONFIG — The remote timeclock
contact input can be configured as a normally open or normally
closed contact. When the timeclock input is ‘On’ the zone will
follow it’s local occupancy schedule. When the timeclock input
is ‘Off’ the zone will be forced into unoccupied state.
Remote Contact
Config: Range Close/Open
Default Value Close
Damper Service Configuration Table — The Damp-
er Service Configuration Table (DAMPER) contains decisions
used to configure the damper minimum, maximum and
ventilation positions. See Table 7.
COOL MINIMUM POSITION This configuration is the
minimum damper position the terminal will control to when
the equipment mode is Cooling (or Fan Only), or free cooling
and the space requirements for cooling are at a minimum.
Cool Minimum
Position: Units %
Range 0 to 100
Default Value 0
COOL MAXIMUM POSITION This configuration is the
maximum damper position the terminal will control to when
the equipment mode is cooling (or fan only), or free cooling
and the space requirements for cooling are at a maximum.
Cool Maximum
Position: Units %
Range 0 to 100
Default Value 100
REHEAT MINIMUM POSITION — This configuration is
for single duct units with ducted reheat. Configure the desired
damper position at which the reheat will provide optimum
performance. This value is compared to the Minimum Cool
value and the greater of the two values is used to determine the
damper position.
Reheat Minimum
Position: Units %
Range 0 to 100
Default Value 0
HEAT MINIMUM POSITION This configuration is the
Minimum damper position the terminal will control to when
the equipment mode is Warm-Up or Heat. If the terminal is not
configured for VAV central heating this is the only position the
terminal will control to for these equipment modes.
Heat Minimum
Position: Units %
Range 0 to 100
Default Value 0
HEAT MAXIMUM POSITION — This configuration is used
to configure the maximum damper position at which the zone
controller will operate if VAV central heat is configured to yes.
If the equipment mode is Heat or Warm-Up and the demand in
the space is for heat the zone controller will calculate the
proper damper position needed to achieve space temperature
set point, operating between the Heat Min and Heat Max.
Heat Maximum
Position: Units %
Range 0 to 100
Default Value 100
VENTILATION POSITION — This configuration is used to
specify the ventilation damper position the terminal will con-
trol to when the air source operating mode is VENT.
Ventilation
Position: Units %
Range 0 to 100
Default Value 30
Holiday Configuration Table — The Holiday Con-
figuration Table (HOLDYxxS) contains decisions used to con-
figure the start date and duration of holidays. See Table 8.
START MONTH The start month is the month in which
the holiday starts. Months are represented by numbers with 1
representing January, 2 February, up to 12.
Start Month: Range 1 to 12
Default Value 1
START DAY The start day is the day on which the holiday
will start.
StartDay: Range 1to31
Default Value 1
DURATION Length of time, in days, that the holiday will
last.
Duration: Range 0 to 365
Default Value 0
Linkage Configuration Table — The Linkage Con-
figuration Table (LINKAGE) contains decisions used to
configure the linkage coordinator zone controller's linkage
settings. This is where the linkage coordinator zone controller,
the air source and the bypass controller options are configured.
It also includes Carrier Network Function Configuration used
for collecting data from multiple controllers and finding the
high, low or average value and transferring the data to another
controller. This table is also used to setup Temperature Sensor
Grouping, which is the sharing of one space temperature sensor
among multiple zone controllers. See Table 9.
LINKAGE MASTER ZONE — This decision defines if the
zone controller will function as a Linkage Coordinator
(Linkage Master) for itself and other zones.
If the zone controller is to use a supply air sensor for
stand-alone operation, this configuration must be configured to
No and the number of Zones to 1.
If the zone controller will use its primary air sensor to deter-
mine the air handler mode for a number of zone controllers,
configure this configuration to Yes, input the number of zones,
and leave the air source decisions at the default values of zero.
If this zone controller will communicate linkage informa-
tion with an air source, configure this configuration to Yes. The
number of zones must be configured and the address of the air
source entered.
Linkage
Master Zone: Range Yes/No
Default Value No
NUMBER OF ZONES This decision defines the number of
zone controllers (including itself) for the Linkage Coordinator to
scan and include as part of the average temperature, set points,
and occupancy information to the air source. The address of the
zone controller functioning as a Linkage Coordinator must be
larger than the number of zones configured. The zone controller
will scan addresses less than its own, including information for
as many zones as are configured. Other zone controller config-
ured as linkage coordinators will also be included, so it is possi-
ble to have zones scanned by more than one linkage coordinator.
Therefore care must be taken in addressing to prevent overlap-
ping systems, unless overlapping systems is necessary. In large
buildings the use of bridges and multiple busses is recommended
to improve communication and provide system differentiation.
Number of
Zones: Range 1 to 32
Default Value 1
Page view 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 315 316

Comments to this Manuals

No comments