Carrier 33ZCVAVTRM Specifications Page 98

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 97
10
APPLICATION NC* LEVELS (RADIATED SOUND) — RECTANGULAR ZONE DAMPERS
*Noise Criteria.
NOTE: The NC values are based on ARI (Air Conditioning and Refrigeration Institute) Standard 885-90 application assumptions.
DAMPER CFM
STATIC PRESSURE
(in. wg)
NC LEVEL
33ZCD1008ZC-01
410
0.01 <20
0.50 30
1.00 45
509
0.03 <20
0.50 30
1.00 40
610
0.07 23
0.50 31
1.00 40
914
0.16 35
0.50 37
1.00 45
33ZCD1408ZC-01
561
0.02 <20
0.50 36
1.00 47
625
0.02 22
0.50 37
1.00 45
725
0.03 25
0.50 38
1.00 45
825
0.05 32
0.50 40
1.00 46
1237
0.11 40
0.50 45
1.00 54
33ZCD1808ZC-01
725
0.01 22
0.50 38
1.00 48
775
0.01 22
0.50 38
1.00 48
874
0.02 28
0.50 40
1.00 48
974
0.02 30
0.50 42
1.00 48
1075
0.03 33
0.50 44
1.00 50
1611
0.06 40
0.50 50
1.00 60
33ZCD2408ZC-01
925
0.01 26
0.50 38
1.00 48
974
0.01 27
0.50 38
1.00 50
1075
0.01 32
0.50 40
1.00 50
1175
0.02 35
0.50 41
1.00 50
1275
0.02 37
0.50 43
1.00 50
1375
0.03 38
0.50 44
1.00 50
2062
0.06 47
0.50 50
1.00 55
Performance data (cont)
Page view 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 315 316