For each period the schedule contains the following fields: Day
of Week, Occupied From, and Occupied To.
DAY OF WEEK The Day of Week configuration consists
of 8 fields corresponding to the 7 days of the week and a holi-
day field in the following order: Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, Sunday, Holiday.
It is displayed as:
M T W Th Fr Sa Su Hol
0 0 0 0 0 0 0 0
If a 1 is configured in the corresponding place for a certain
day of the week, the related “Occupied from” and “Occupied
to” times for that period will take effect on that day of the
week. If a 1 is placed in the holiday field, the related times will
take effect on a day configured as a holiday. A zero means the
schedule period will not apply to that day.
Day of week: Range 0 or 1
Default Values 11111111 for period 1,
00000000 for the rest of
the periods
OCCUPIED FROM This field is used to configure the
hour and minute, in military time, that the mode for the
PremierLink™ controller will switch to occupied.
Occupied From: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 00:00
OCCUPIED TO This field is used to configure the hour
and minute, in military time, that the mode for the PremierLink
controller switches from occupied to unoccupied.
Occupied To: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 24:00
Table 16 — Occupancy Configuration
Set Point Screen — The Set Point screen is used to con-
figure the occupied and unoccupied set points. See Table 17.
OCCUPIED LOW The Occupied Low set point describes
the low temperature limit of the space during Occupied mode.
Occupied Low: Units degrees F (degrees C)
Range 40.0 to 90.0
Default Value 70.0
OCCUPIED HIGH The Occupied High set point describes
the high temperature limit of the space during Occupied mode.
Occupied High: Units degrees F (degrees C)
Range 45.0 to 99.9
Default Value 74.0
UNOCCUPIED LOW The Unoccupied Low set point
describes the low temperature limit of the space during
Unoccupied mode. The cooling mode will be turned on when
the space temperature achieves this value plus the unoccupied
cooling deadband. The cooling mode will be turned off when
the space temperature goes below this value.
Unoccupied Low: Units degrees F (degrees C)
Range 40.0 to 90.0
Default Value 75.0
UNOCCUPIED HIGH The Unoccupied High set point de-
scribes the high temperature limit of the space during Unoccu-
pied mode. The heating mode will be turned on when the space
temperature achieves this value minus the unoccupied heating
deadband. The heating mode will be turned off when the space
temperature goes above this value.
Unoccupied High: Units degrees F (degrees C)
Range 45.0 to 99.9
Default Value 90.0
HIGH OAT LOCKOUT FOR TSTAT — This is the high
outdoor air lockout temperature for thermostat mode. In ther-
mostat mode, the OAT must be below this value and below
OAT max for free cooling from the economizer.
Hi OAT Lckout
for TSTAT: Units degrees F (degrees C)
Range 55.0 to 75.0
Default Value 65.0
UNOCCUPIED OAT LOCKOUT TEMPERATURE —
The Unoccupied OAT Lockout Temperature describes the low-
est outdoor-air temperature allowed for Unoccupied Free
Cooling operation. This function is also used by IAQ Pre-
Occupancy Purge control to determine the minimum damper
position for IAQ purge.
Unoccupied
OAT Lockout: Units degrees F (degrees C)
Range 40.0 to 70.0
Default Value 50.0
UNOCCUPIED HEATING DEADBAND — The Unoccu-
pied Heating Deadband describes the value that is subtracted
from the unoccupied heating set point that the space tempera-
ture must achieve before unoccupied heating mode will be
turned on.
Unoccupied
Heating
Deadband: Units delta degrees F
(delta degrees C)
Range 0.0 to 10.0
Default Value 1.0
UNOCCUPIED COOLING DEADBAND — The Unoccu-
pied Cooling Deadband describes the value that is added to the
unoccupied cooling set point that the space temperature must
achieve before unoccupied cooling mode will be turned on.
DESCRIPTION VALUE UNITS NAME
Manual Override Hours 0 hours OVRD
Period 1: Day of Week 11111111 DOW1
Period 1: Occupied from 00:00 OCC1
Period 1: Occupied to 24:00 UNOCC1
Period 2: Day of Week 00000000 DOW2
Period 2: Occupied from 00:00 OCC2
Period 2: Occupied to 24:00 UNOCC2
Period 3: Day of Week 00000000 DOW3
Period 3: Occupied from 00:00 OCC3
Period 3: Occupied to 24:00 UNOCC3
Period 4: Day of Week 00000000 DOW4
Period 4: Occupied from 00:00 OCC4
Period 4: Occupied to 24:00 UNOCC4
Period 5: Day of Week 00000000 DOW5
Period 5: Occupied from 00:00 OCC5
Period 5: Occupied to 24:00 UNOCC5
Period 6: Day of Week 00000000 DOW6
Period 6: Occupied from 00:00 OCC6
Period 6: Occupied to 24:00 UNOCC6
Period 7: Day of Week 00000000 DOW7
Period 7: Occupied from 00:00 OCC7
Period 7: Occupied to 24:00 UNOCC7
Period 8: Day of Week 00000000 DOW8
Period 8: Occupied from 00:00 OCC8
Period 8: Occupied to 24:00 UNOCC8