22
shall not allow reheat to function unless the zone has
a valid supply air sensor.
E. If a linkage master loses communications with the
equipment controller and it has a primary air tem-
perature sensor installed, the linkage master zone
controller shall determine the equipment operating
mode based on the temperature of the primary air,
and the system pressure measured at the bypass
controller. If no bypass controller exists, the air
source will be determined to be always on.
F. If a linkage master loses communication with an
associated zone controller, the linkage master shall
alarm and remove that zone temperature from its
weighted averages. The zone controller shall con-
tinue to operate in a stand-alone mode.
Part 5 — System
5.01 The system shall include the ability to configure and
display up to 32 zones for each air source. A zone
shall be defined as a space temperature sensor wired
to a zone controller.
A. Configuration:
Each zone shall have the ability to configure and dis-
play the following:
1. Minimum/Maximum damper position limits
used by the terminal control when the air
source is in the Cooling mode.
2. Minimum/Maximum damper position limits
used by the terminal control when the air
source is in the Heating mode.
3. Reheat damper position limit (single duct units
only) used when local heat is required and the
air source is in Cooling mode.
4. Ventilation damper position when air source is
in cooling or free cooling mode.
5. Terminal Inlet size (diameter or square inches).
6. Heating type.
7. Central Heating caller.
8. Heat on delay.
9. Fan off delay (parallel terminal fans only).
10. Maximum duct temperature.
11. Alarm set points.
12. Occupancy Override value.
13. Heating and cooling Occupied/Unoccupied
temperature set points.
14. Ventilation set point (CO
2) and maximum
damper position limit.
15. Heat enable/disable.
B. Zone Display:
Zones shall have the capability to display the follow-
ing as a minimum:
1. Terminal operating mode and terminal type.
2. Zone space temperature.
3. Actual damper blade position (0 to 100%
open).
4. Primary air temperature (if applicable).
5. Terminal fan status (if applicable).
6. Leaving temperature (heating only).
7. Zone CO
2 (if applicable).
8. Zone Relative Humidity (if applicable).
C. Maintenance Display:
Maintenance screens shall be provided to ease and
expedite the task of troubleshooting. The screens
shall have the capability to display the following as a
minimum:
1. The current calculated damper reference.
2. Occupancy and override status.
3. Current user set point offset value.
4. Current heating and cooling set points.
5. Heat Status (if applicable).
6. Ducted heating reference temperature.
7. Current Air Source operating mode and supply
temperature.
8. Average zone temperature, average occupied
zone temperature, and the next occupied/
unoccupied day and time for all terminals
serviced by each respective air handler (linkage
master only).
9. Occupancy maintenance screens shall display
such information as timed override status and
duration and current occupied and unoccupied
time (Local schedule only).
10. Position of the open primary air damper of all
terminals serviced by their respective air han-
dler (coordinator only).
Part 6 — Linkage
6.01 Each zone controller shall have the capability to
directly communicate to a factory supplied air
source microprocessor to provide a totally linked
and coordinated Air Distribution System.
A. The linkage shall include the following air source
modes for use by the Coordinator as a minimum:
Off, Cooling, Heating, Night Time Free Cooling,
Pressurization, and Evacuation.
B. The linkage shall also provide system data to the air
source controller for use in its algorithms.
C. The coordinator shall periodically poll its assigned
zones to acquire their updated values.
D. Space temperature and space temperature set
points acquired by the coordinator for use by the air
handler controller shall include a weighted factor,
proportional to the size of the zone.
E. Only those zones with valid temperature readings
shall be included.
F. The system data shall include average zone tempera-
ture, average occupied zone temperature, average
occupied and unoccupied heat/cool set points,
occupancy status, and the next occupied zones ter-
minal time and day.
Guide specifications — 3V™ control system (cont)