43
Global Override
Enable: Range No/Yes
Default Value Yes
LINKAGE THERMOSTAT The Linkage Thermostat start
time biases allow the installer to configure the time per degree
the space should take to recover in the Heat and Cool modes
for optimum start with a Linkage Thermostat, 3V™ control
system, or an attached SPT sensor. These numbers will be used
to calculate the Start Bias time. The value entered is deter-
mined by the mass of the zone. Typically, a value of 10 (the de-
fault), will be adequate for most applications. For higher mass
areas, such as a store lobby, the value may be increased to 20 or
25.
Cool Start Bias: Units minutes/degree
Range 0 to 60
Default Value 10
Heat Start Bias Units minutes/degree
Range 0 to 60
Default Value 10
FILTER TIMER HOURS — The Filter Timer Hours config-
uration determines when the filter status will display a “Dirty”
alarm. When the Filter Timer Hours is configured to a value
other than zero and fan run time exceeds the value configured,
the filter status will display “Dirty” and a CCN alarm will be
generated. Resetting the configured Filter Timer Hours value to
zero will disable the alarm condition. The value of the timer is
stored in EEPROM to protect it in the event of a power failure.
The value is stored every 24 hours.
If configured for 0, an optional normally open filter status
switch can be read when connected the Filter Status input. Fil-
ter status will display "Clean" when open and "Dirty" when
closed.
Filter Timer
Hours: Range 0 to 99
Default Value 15 (where 15*100=1500)
INDOOR AIR QUALITY PRIORITY LEVEL — The
Indoor Air Quality Priority Level, when set to Low, ensures
that comfort is not being compromised by bringing in too much
outdoor air to maintain IAQ set point. When an override condi-
tion takes place, IAQ control is disabled, and Economizer
Minimum Position is set to the user configured value MDP.
When set to High, IAQ control is always active regardless of
indoor comfort conditions. The controller will temper cold air
(OAT <55 F) to prevent cold blow.
Indoor Air Quality
Priority Level: Range High/Low
Default Value Low
INDOOR AIR QUALITY PREOCCUPANCY PURGE —
The Indoor Air Quality Preoccupancy Purge brings in fresh
outdoor air before the Occupied mode begins. The IAQ Pre-
Occupancy Purge is used to lower carbon dioxide levels below
the IAQ set point before Occupied mode starts.
The purge is started 2 hours before the occupied time and
lasts for the specified duration.
Indoor Air Quality
Preoccupancy
Purge: Range Disable/Enable
Default Value Disable
INDOOR AIR QUALITY PURGE DURATION — The
Indoor Air Quality Purge Duration specifies the duration of
IAQ Pre-Occupancy purge. The purge is started 2 hours
before the occupied time and lasts for the specified duration.
Indoor Air Quality
Purge Duration: Display Units minutes
Display Range 0 to 60
Default Value 5
INDOOR AIR QUALITY DELTA SET POINT — The
Indoor Air Quality Delta Set Point specifies the highest
Indoor Air Quality level (measured in ppm) allowed within the
space whenever unit is in Occupied mode (or Supply Fan On
for units with Thermostat control) and Indoor Air Quality
sensor is installed.
Indoor Air Quality
Delta Set Point: Display Units PPM
(parts per million)
Display Range 1 to 5000
Default Value 650
INDOOR AIR QUALITY MAXIMUM DAMPER POSI-
TION This point displays upper limit of the Indoor Air
Quality minimum damper position calculated by the IAQ
control.
For example, if IAQ is calculating 100% Minimum Damper
Position, but this decision is set to 50%, then the IAQ Mini-
mum Damper Position will be clamped to 50%.
NOTE: When IAQ priority is set to HIGH, this value must
reflect the maximum outdoor air percentage that the equipment
can heat or cool at worst conditions.
Indoor Air Quality
Maximum Damper
Position: Display Units % damper open
Display Range 0 to 100%
Default Value 50%
INDOOR AIR QUALITY SENSOR — The indoor air quality
sensor defines the value in parts per million (ppm) which cor-
relate to the low and high voltage readings from the sensor.
Low Reference specifies the low point of the Indoor IAQ
Sensor range in ppm.
Low Reference: Units PPM (parts per million)
Range 0 to 5000
Default Value 0
High Reference specifies the high point of the Indoor IAQ
Sensor range in ppm.
High Reference: Units PPM (parts per million)
Range 0 to 5000
Default Value 2000
OUTDOOR AIR QUALITY SENSOR — The outdoor air
quality sensor defines the value in parts per million (ppm)
which correlate to the low and high voltage readings from the
sensor.
Low Reference specifies the low point of the Outdoor IAQ
Sensor Range in ppm.
Low Reference: Units PPM (parts per million)
Range 0 to 5000
Default Value 0
High Reference specifies the high point of the Outdoor IAQ
Sensor Range in ppm.
High Reference: Units PPM (parts per million)
Range 0 to 5000
Default Value 2000
OUTDOOR AIR QUALITY LOCKOUT POINT — When
set to non-zero value, the IAQ algorithm will compare Outdoor
IAQ reading against this decision and disable IAQ control
whenever the value of OAQ exceeds this configured value.
Outdoor Air
Quality Lockout
Point: Range 0 to 5000
Default Value 0