20
Note: Pins 17 and 18 of Connector J3 are 24 Vdc sources for
internally powered (2-wire) milliamp sensors. Each pin can
provide power for up to four sensors maximum. Powering
other devices could damage the Universal Controller.
The T-56 can be wired to any two channels.
1
2
1
2
TH
COM
SW
CH. A
CH. B
Note: You should configure channel B as a setpoint offset hardware
input type point.
When wiring the Automation Components Inc. 10K-CP (Carrier part
number 33ZCT56SPT) sensor with slidebar, follow the guidelines below:
The sensor requires one temperature input hardware point and one
setpoint offset point on the Universal Controller, one for the ther-
mistor and one for the slidebar.
Wire both inputs to the same controller, and run a 3-wire cable to the
sensor.
The ACI sensor has four terminals. The second SEN terminal (on
left), and the first (SET) terminal (on right) should be jumpered
(common wire).
Since there is a common for both signals and both inputs wired to the
same module, do not jumper the signal commons on the controller
(pin 2 of both channels).
Wiring T-56 Space
Temperature Sensor
Wiring ACI 10K-AN
and 10K-CP Sensors