41
Fan Off Delay
The Fan Off Delay configuration is used to
define a delay time. The delay time is from when the heat is de-
activated (in a parallel terminal) until the parallel fan is deacti-
vated. This allows the fan to circulate air and remove the resid-
ual heat from the heat source.
Fan Off Delay: Units minutes
Range 1 to 15
Default Value 2
Two-Position Heat Logic
This configuration is used for
controlling a normally closed or normally open valve for hot
water. Use normal logic if the valve is normally closed. Use in-
verted logic if the valve is normally open.
Two Position
Heat Logic: Range Normal/Invert
Default Value Normal
Space Temperature Trim
This configuration is used to trim
a space sensor which might need calibration. For example, if
the temperature displayed is two degrees above the value mea-
sured with calibrated test equipment, input a value of 2.0.
Space Temperature
Trim: Units delta F (delta C)
Range 9.9 to 9.9
Default Value 0.0
Supply Air Temperature Trim
This configuration is used
to trim a supply air sensor which might need calibration. For
example, if the temperature displayed is two degrees above the
value measured with calibrated test equipment, input a value of
2.0.
Supply Air Temperature
Trim: Units delta F (delta C)
Range 9.9 to 9.9
Default Value 0.0
Remote Contact Config
The remote timeclock contact in-
put can be configured as a normally open or normally closed
contact. When the timeclock input is On the zone will follow
its local occupancy schedule. When the timeclock input is
Off the zone will be forced into unoccupied state.
Remote Contact
Config: Range Close/Open
Default Value Close
OPTIONS SERVICE CONFIGURATION SCREEN
The Options Service Configuration screen is used to configure
the service options of the air terminal controller. See Table 11.
Occupancy Schedule Number
The Occupancy Schedule
Number defines what Occupancy schedule the zone controller
will use. Occupancy Schedule 64 is a local schedule. Occupan-
cy Schedules 65 to 99 are global schedules.
Occupancy Schedule
Number: Range 64 to 99
Default Value 64
Global Schedule Master
The Global Schedule Master con-
figuration allows the Occupancy Schedule to be used as a Glo-
bal Schedule Master (Occupancy Schedules 65-99).
Global Schedule
Master: Range No/Yes
Default Value No
Override
The Override parameter is used to configure the
number of hours and minutes the override will be in effect. The
user initiates override by pressing the override button on the
space temperature sensor. This will cause the schedule to enter
into the Occupied mode. If global scheduling is used, all zones
using the global schedule will enter Occupied mode. Pushing
the override button during Occupied mode will have no effect.
If the occupancy override is due to end after the start of the
next occupancy period, the mode will transition from occupan-
cy override to occupied without becoming unoccupied, and the
occupancy override timer will be reset.
NOTE: If using the tenant billing function, the override
hours set point must be configured between 1 and 3 hours.
Override: Units Hours: Minutes
Range 00:00 to 24:00
Default Value 00:00
Broadcast Acknowledger
This configuration defines if the
zone controller will be used to acknowledge broadcast messag-
es on the CCN bus. One broadcast acknowledger is required
per bus, including secondary busses created by the use of a
bridge.
Broadcast
Acknowledger: Range No/Yes
Default Value No
Table 11 Options Service Configuration Screen
DESCRIPTION DEFAULT POINT NAME
Occupancy Schedule Number
64 SCH
Global Schedule Master
No GSM
Override
00:00 OVR
Broadcast Acknowledge
No BCACK
Set Point Group Number
0SETT
Global Set Point Master
No GSTM
Maximum Offset Adjust
2 F LIMT
Control Options
0CTLOPT
Humidity
Proportional Gain
Integral Gain
Maximum Output Value
1.5
0.30
100.0 cfm
KP
KI
MAXOUT
Air Quality
Proportional Gain
Integral Gain
Maximum Output Value
0.10
0.03
100.0 cfm
KP
KI
MAXOUT
AQ Low Voltage
0.0 AQINLO
AQ High Voltage
10.0 AQINHI
AQ Low Reference
0 ppm AQLO
AQ High Reference
2000 ppm AQHI
801