START-UP
Use the Carrier network communication software to start up
and configure the PremierLink controller.
Changes can be made using the ComfortWORKS
®
soft-
ware, ComfortVIEW™ software, Network Service Tool, Sys-
tem Pilot™ device, or Touch Pilot™ device. The System Pilot
and Touch Pilot are portable interface devices that allow the
user to change system set-up and set points from a zone sensor
or terminal control module. During start-up, the Carrier soft-
ware can also be used to verify communication with Premier-
Link controller.
NOTE: All set-up and set point configurations are factory-
set and field-adjustable.
For specific operating instructions, refer to the literature
provided with user interface software.
Perform System Check-Out
1. Check correctness and tightness of all power and
communication connections.
2. At the unit, check fan and system controls for proper
operation.
3. At the unit, check electrical system and connections of
any optional electric reheat coil.
4. Check to be sure the area around the unit is clear of
construction dirt and debris.
5. Check that final filters are installed in the unit. Dust and
debris can adversely affect system operation.
6. Verify that the PremierLink controls are properly
connected to the CCN bus.
Initial Operation and Test — Perform the following
procedure:
1. Apply 24 vac power to the control.
2. Connect the service tool to the phone jack service port of
the controller.
3. Using the Service Tool, upload the controller from
address 0, 31 at 9600 baud rate. The address may be set at
this time. Make sure that Service Tool is connected to
only one unit when changing the address.
MEMORY RESET DIP switch 4 causes an E-squared
memory reset to factory defaults after the switch has been
moved from position 0 to position 1 and the power has been
restored. To enable the feature again, the switch must be put
back to the 0 position and power must be restored; this pre-
vents subsequent resets to factory defaults if the switch is left
at position 1.
To cause a reset of the non-volatile memory (to factory
defaults), turn the controller power off if it is on, move the
switch from position 1 to position 0, and then apply power to
the controller for a minimum of 5 seconds. At this point, no
action occurs, but the controller is now ready for the memory
to reset. Remove power to the controller again and move the
switch from position 0 to position 1. This time, when power is
applied, the memory will reset to factory defaults. The control-
ler address will return to bus 0 element 31, indicating that
memory reset occurred.
Sequence of Operation
THERMOSTAT MODE If the PremierLink™ controller is
configured for Thermostat mode (TSTAT), it will control only
to the thermostat inputs on J4. These inputs can be overridden
through CCN communication via the CV_TSTAT points dis-
play table. When in this mode, the fire safety shutdown (FSD)
4
3
5
2
8
6
7
1
10
11
9
12
PINK
VIOLET
BLACK
BLUE
YELLOW
NOTE 1
NOTE 3
RUN
500 OHM
RESISTOR
50HJ540573
ACTUATOR
ASSEMBLY
RED
WHITE
ECONOMISER2 PLUG
DIRECT DRIVE
ACTUATOR
4-20mA SIGNAL
WIRES FOR
OAT SENSOR
4-20 mA
TO J9 ON
PremierLink
BOARD
24 VAC
TRANSFORMER
GROUND
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen
-
sor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
Fig. 34B — PremierLink™ Control Wiring to Belimo-Style Actuator EconoMi$er2 Harness
The unit must be electrically grounded in accordance with
local codes and NEC ANSI/NFPA 70 (American National
Standards Institute/National Fire Protection Association).