24
5 4 3 2 1
VDC
0-10
DA
FIXED
—
mA
2-10
RA
AUTO
6-9
MOVE TO LEFT
FOR 4-20mA CONTROL
WITH PREMIERLINK
CONTROLLER
Fig. 32 — Position of Actuator Mode Switches
(Factory Default)
Output 20 VDC at 25 mA
Feedback 0 (2)-10 or 6-9 VDC
Input 0 (2)-10 or 6-9 VDC, 0 (4)-20 mA
24 VAC/VDC
COM
(3)
(5)
(4)
(2)
(1)
J9-1
TO 24V
TRANSFORMER
Gray
White/Red
Red
Yellow
White
WIRE HARNESS
FROM ACTUATOR
24 VAC
TRANSFORMER
GROUND
4-20mA TO
J9-1 ON
PREMIERLINK
CONTROLLER
ECONOMIZER
12-PIN HARNESS
ACTUATOR
50TJ400812
M9206-GGC-2
Fig. 33 — PremierLink™ Controller Wiring to
Economizer Actuator With Wire Harness (M9206-GGC-2)
Fig. 34A — PremierLink Control Wiring to Johnson Actuator Economizer Harness