HUMIDITY SENSOR (WALL-MOUNTED) INSTALLA-
TION The accessory space humidity sensor is installed on
an interior wall to measure the relative humidity of the air with-
in the occupied space.
The use of a standard 2 x 4-in. electrical box to accommo-
date the wiring is recommended for installation. The sensor can
be mounted directly on the wall, if acceptable by local codes.
If the sensor is installed directly on a wall surface, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field-supplied). Do not over tighten screws. See Fig. 14.
The sensor must be mounted vertically on the wall. The
Carrier logo should be oriented correctly when the sensor is
properly mounted.
Avoid corner locations. Allow at least 4 ft between the sen-
sor and any corner. Airflow near corners tends to be reduced,
resulting in erratic sensor readings. The sensor should be verti-
cally mounted approximately 5 ft up from the floor, beside the
space temperature sensor.
For wiring distances up to 500 feet, use a 3-conductor, 18 or
20 AWG cable. A CCN communication cable can be used, al-
though the shield is not required. The shield must be removed
from the sensor end of the cable if this cable is used. See
Fig. 15 for wiring details.
The power for the sensor is provided by the PremierLink
control on terminal J5-4 (+33 to +35vdc). To wire the sensor
perform the following:
1. At the sensor, remove 4-in. of jacket from the cable. Strip
1
/
4
-in. of insulation from each conductor. Route the cable
through the wire clearance opening in the center of the
sensor. See Fig. 14.
2. Connect a field-supplied BLACK wire to the sensor
screw terminal marked Vin.
3. Connect a field-supplied RED wire into the sensor screw
terminal marked Io.
4. At the PremierLink controller, route the cable away from
high voltage wiring and disconnect the power to prevent
accidental shorting or grounding of wires when connect-
ing the sensor. Remove the J5 Molex female plug and lo-
cate the BROWN wire on pin 3. Using a small, flat blade
screwdriver gently press down in the slot on the side of
the plug while pulling on the BROWN wire to remove it
from slot. Re-insert the BROWN wire in the pin 4 slot
making sure it is securely seated. There should now be an
empty slot between the BLUE and BROWN wires. See
Fig. 15.
5. Connect the field-supplied RED wire from the sensor to
the BLUE wire on J5-4.
6. Connect the field-supplied BLACK wire from the sensor
to the BROWN wire on J5-2.
Do NOT clean or touch the sensing element with chem-
ical solvents as they can permanently damage the sensor.
DO NOT mount the sensor in drafty areas such as near
heating or air-conditioning ducts, open windows, fans, or
over heat sources such as baseboard heaters, radiators, or
wall-mounted light dimmers. Sensors mounted in those ar-
eas will produce inaccurate readings.
8
7
6
5
4
32
1
2
1
HG
24 VAC
OR
24 VDC
NC
ALARM
RELAY
CONTACTS
COM
NO
}
0-10VDC
SIG COM (J5-3)
4-20mA (J5-2)
+
+
-
+
-
Fig. 12 — Outdoor Air Quality (CO
2
) Sensor
(33ZCSENCO2) — Typical Wiring Diagram
COVER REMOVED SIDE VIEW
Fig. 13 — Outdoor Air Quality Sensor Cover
SW2
12345 6
ON
Io
Vin
Gnd
Vo
MOUNTING
HOLES
WIRING
OPENING
Fig. 14 — Humidity Sensor Installation
a33-9141