When connecting the CCN Communication Bus to a system element,
each of the three conductors must be used for the same signal type
throughout the entire CCN. That is:
signal (+) terminals must always be wired to signal (+)
signal ground terminals must always be wired to signal ground
signal (-) terminals must always be wired to signal (-)
To achieve this consistancy, the following color code system is recom-
mended:
Signal Type Conductor Insulation Color/Pin #
+ Red (1)
Ground White (2)
- Black (3)
If a cable with a different color scheme is selected for the CCN Commu-
nication Bus, a similar color code system should be adopted to simplify
installation and checkout.
At each system element, the shields of its communication bus cables must
be tied together. If the CCN Communication Bus is entirely within one
building, the resulting continuous shield must be connected to ground at
only one single point (refer to Figure 7). If the CCN Communication Bus
exits from one building and enters another, its shields must also be
connected to ground at a lightning suppressor in each building.
The specific shield connections are illustrated on the following pages in
the wiring description for each system element type.
Grounding of Bus
Shields