32
Table 11 — Points Display
NOTE: Bold values indicate points that can be forced through communications.
SUPPLY FAN RELAY This point displays the command-
ed state of the Supply Fan Relay.
Supply Fan
Relay: Display Units Discrete ASCII
Default Value Off
Display Range Off/On
Network Access Read/Write
SUPPLY FAN STATUS — This point displays the Supply
Fan status if controller is configured to receive input from the
Supply Fan. Otherwise this point will display the output state
of the Supply Fan Relay. This mode can only be used when the
controller is in sensor control mode.
Supply Fan
Status: Display Units Discrete ASCII
Default Value Off
Display Range Off/On
Network Access Read Only
ECONOMIZER DAMPER POSITION This point dis-
plays the current commanded damper position of the
economizer 4 to 20 mA on the J-9 connector. The 4 to 20 mA
signal is scaled linearly over the range of 0 to 100% of the Sup-
ply Fan Relay.
Economizer
Position: Display Units % Open
Default Value 0
Display Range 0 to 100
Network Access Read/Write
CURRENT MINIMUM DAMPER POSITION — This point
displays the current minimum damper position if an Indoor Air
Quality routine is not active. If an Indoor Air Quality sensor is
installed and the differential air quality set point has been
exceeded, this point will display the current calculated mini-
mum position deemed necessary to maintain the air quality in
the space.
Current Minimum
Damper Position: Display Units % Open
Default Value 0
Display Range 0 to 100
Network Access Read Only
FILTER STATUS The filter status point will be shown as
“CLEAN” until the run time of the fan exceeds the configured
Filter Timer Hours or the filter switch is closed. When the user-
configured Filter Timer Hours has been exceeded, the Filter
Status will display “DIRTY” and a CCN alarm will be generat-
ed. Forcing the point to “CLEAN” will clear the alarm condi-
tion and will reset the timer. (Setting the configured filter timer
value to zero will provide the same function.) The value of the
timer is stored in EEPROM to protect it in the event of a power
failure. This is done periodically every 24 hours. The filter tim-
er function only operates if the configured filter timer value
(FLTTMR) is a non-zero number. If a filter switch is used, then
“CLEAN” will be shown when the switch is open.
Filter Status: Display Units Discrete ASCII
Default Value Clean
Display Range Clean/Dirty
Network Access Read/Write
REMOTE OCCUPIED MODE This point displays the
status of the remote timeclock input or a remote door switch
contact. This input is only available when the controller is be-
ing used in sensor control mode. When configured for Remote
Contact, if the point is ON and the controller is not controlled
by a 3V™ Linkage, the controller will function in an occupied
DESCRIPTION VALUE UNITS STATUS FORCE NAME
Space Temperature 72.2 dF SPT
Supply Air Temperature 67.1 dF SAT
Outdoor Air Temperature 48.8 dF OAT
Control Setpoint 70.0 dF CLSP
Rooftop Mode COOL MODE
Cooling % Total Capacity 0 % CCAP
Heating % Total Capacity 0 % HCAP
Economizer Active Yes ECOS
Supply Fan Relay On SF
Supply Fan Status On SFS
Economizer Position 26.2 % ECONPOS
Current Min Damper Pos 20 % IQMP
Filter Status Clean FLTS
Remote Occupied Mode Off RMTOCC
Heat Stage 1 Off HS1
Heat Stage 2 Off HS2
Ht 3/Exhaust/Rev Valv/DH Off H3_EX_RV
Enthalpy Low ENTH
Indoor Air Quality 367.9 IAQI
Indoor Air Quality Setpt 1050.0 IAQS
Outdoor Air Quality 0.0 Sensor failure OAQ
Indoor RH 0 %IRH
Fire Shutdown Normal FSD
SPT Offset 0.0 ^F STO
Compressor 1 Off CMP1
Compressor 2 Off CMP2
Compressor Safety Off CMPSAFE
Rooftop Mode 2 RTU_MODE
LON Setpoint 72 dF LON_SP
Alarm Status Normal ALARM