31
capacity equal to the stage of capacity that the unit is operating
at when the redline alert was initiated.
When load shed command is received the control will re-
duce capacity as shown in Tables 9 and 10.
Table 9 — Load Shed Command — Gas and
Electric Heat Units
Table 10 — Load Shed Command — Heat Pump
Units
The controller will have a maximum demand limit timer of
1 hour that prevents the unit from staying in load shed or red-
line alert longer than 1 hour in the event the controller loses
communication with the network load shed module. Should the
maximum demand limit timer expire prior to receiving the un-
shed device command from CCN, the control will stop demand
limit mode and return to normal operation.
CONFIGURATION
The following sections describe the computer configuration
screens which are used to configure the PremierLink™ con-
troller. The screens shown may be displayed differently when
using different Carrier software.
Points Display Screen — The Points Display screen is
used to monitor and change the PremierLink controller set
points. See Table 11.
SPACE TEMPERATURE This point displays the space
temperature from the 10K thermistor (Type II) located in the
space.
Space
Temperature: Display Units degrees F (degrees C)
Default Value –40.0
Display Range –40.0 to 245.0
Network Access Read/Write
SUPPLY AIR TEMPERATURE — The Supply Air Temper-
ature point displays the temperature of the air leaving the unit,
downstream of any cool or heat sources. Temperature is mea-
sured by a 10K thermistor (Type II). This sensor is required for
proper function of the heating, cooling, and the economizer.
Supply Air
Temperature: Display Units degrees F (degrees C)
Default Value 0.0
Display Range –40.0 to 245.0
Network Access Read/Write
OUTDOOR AIR TEMPERATURE — Temperature of the
air entering the rooftop is measured by a 10K thermistor (Type
II). This sensor is required for proper function of the cooling
mode and the economizer.
Outdoor Air
Temperature: Display Units degrees F (degrees C)
Default Value 0.0
Display Range –40.0 to 245.0
Network Access Read/Write
CONTROL SET POINT This point displays the current
controlling set point when a heat or cool mode is active. If there
is not an active heat or cool set point, the set point of the last
mode is displayed. Upon reset or start-up, the proper cooling
set point is displayed, depending on occupancy. In the thermo-
stat mode, this point is not used for equipment control.
Control Set Point: Display Units degrees F (degrees C)
Default Value Unoccupied Cool
Setpoint
Display Range 35 to 110
Network Access Read Only
ROOFTOP MODE This point displays the current mode
of the PremierLink controller based on active space tempera-
ture, set points, and occupancy.
Rooftop Mode: Display Units ASCII
Default Value Off
Display Range OFF, COOL, HEAT,
FAN ONLY,
UNOCCOOL,
UNOCHEAT,
WA RM UP,
FREECOOL, PRESS
EVAC
Network Access Read Only
COOLING PERCENT TOTAL CAPACITY — The Cooling
Percent Total Capacity point is used to display the current
Cooling Capacity. When cooling is enabled, the percent of
cooling being delivered is determined by the following formula
for the number of compressor stages confirmed:
% Output Capacity = (no. of active stages/Total stages) * 100.
Cooling Percent
Total Capacity: Display Units % output capacity
Default Value 0
Display Range 0 to 100
Network Access Read Only
HEATING PERCENT TOTAL CAPACITY — The Heat-
ing Percent Total Capacity point is used to display the current
Heating Capacity.
When heat is enabled, the percent of heat being delivered is
determined by the following formula for gas or electric heat:
% Output Capacity = (no. of active stages/Total stages) * 100
Heating Percent
Total Capacity: Display Units % output capacity
Default Value 0
Display Range 0 to 100
Network Access Read Only
ECONOMIZER ACTIVE — The Economizer Active point
displays the status of the economizer for free cooling. When
the outdoor conditions match the desired indoor conditions, the
economizer will be enabled for outdoor air assisted cooling.
Economizer
Active: Display Units Discrete ASCII
Default Value No
Display Range No/Yes
Network Access Read Only
CURRENT CAPACITY NEW CAPACITY
CMP1 DX Cooling OFF
CMP1+CMP2 CMP1
HS1 Heat OFF
HS1+HS2 (+HS3) HS1
CURRENT CAPACITY NEW CAPACITY
Cooling:
CMP1 DX Cooling OFF
CMP1+CMP2 CMP1
Heating:
CMP1+CMP2+RV Heat OFF
CMP1+CMP2+RV+HS1+HS2 CMP1+CMP2+RV