G. Maximum CO2 or space relative humidity shall be
supplied to the air source through other networking
means.
H. The system shall provide the capability of using the
above data in the air source algorithms for adaptive
optimal start, Night Time Free Cooling, dehumidifi-
cation and Demand Controlled Ventilation adjust-
ments to the mixed air damper routine.
I. The air handler controller shall, through the Air
Distribution System, bias its occupancy time sched-
ules to provide optimization routines and occupant
override.
J. For those systems that do not include inherent link-
age software, the Coordinator shall determine the
operational mode of the equipment through its asso-
ciated bypass controller pressure sensor and a tem-
perature sensor mounted in the supply ductwork. If
there is no bypass controller then the system will
assumed to be always on.
K. The vendor shall make it clear in the bid/proposal if
linkage software is not going to be part of their
offering.