Install Sensors — The PremierLink™ controller can be
used with either the T58 communicating sensor or any combi-
nation of CO
2
and space temperature sensors. Refer to the in-
structions supplied with each sensor for electrical require-
ments.
NOTE: All sensors are field-installed accessories.
SPACE TEMPERATURE (SPT) SENSOR INSTALLA-
TION There are four types of SPT sensors available from
Carrier: The 33ZCT55SPT space temperature sensor with
timed override button, the 33ZCT56SPT space temperature
sensor with timed override button and set point adjustment, the
33ZCT58SPT T58 communicating room sensor with timed
override button, set point adjustment, and manual fan control,
and the 33ZCT59SPT space temperature sensor with LCD
screen, override button, and set point adjustment.
The space temperature sensors are used to measure the
building interior temperature. The T58 communicating room
sensors measure and maintain room temperature by communi-
cating with the controller. Sensors should be located on an
interior building wall. The sensor wall plate accommodates the
NEMA (National Electrical Manufacturers Association)
standard 2 x 4 junction box. The sensor can be mounted direct-
ly on the wall surface if acceptable by local codes.
Do not mount the sensor in drafty locations such as near air
conditioning or heating ducts, over heat sources such as base-
board heaters, radiators, or directly above wall-mounted light-
ing dimmers. Do not mount the sensor near a window which
may be opened, near a wall corner, or a door. Sensors mounted
in these areas will have inaccurate and erratic sensor readings.
The sensor should be mounted approximately 5 ft from the
floor, in an area representing the average temperature in the
space. Allow at least 4 ft between the sensor and any corner
and mount the sensor at least 2 ft from an open doorway. The
SPT sensor wires are to be connected to terminals in the unit
main control board.
Install the sensor as follows:
1. Locate the 2 Allen type screws at the bottom of the
sensor.
2. Turn the two screws clockwise to release the cover from
the sensor wall mounting plate.
3. Lift the cover from the bottom and then release it from
the top fasteners.
4. Feed the wires from the electrical box through the open-
ing in the center of the sensor mounting plate.
5. Using two no. 6-32 x 1 mounting screws (provided with
the sensor), secure the sensor to the electrical box.
NOTE: Sensor may also be mounted directly on the
wall using 2 plastic anchors and 2 sheet metal screws
(field-supplied).
6. Use 20 gage wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three-conductor shielded cable for the sensor and set
point adjustment connections. The standard CCN
communication cable may be used. If the set point adjust-
ment (slidebar) is not required, then an unshielded, 18 or
20 gage, two-conductor, twisted pair cable may be used.
The CCN network service jack requires a separate,
shielded CCN communication cable. Always use sepa-
rate cables for CCN communication and sensor wir-
ing. (Refer to Fig. 3-6 for wire terminations.)
7. Replace the cover by inserting the cover at the top of the
mounting plate first, then swing the cover down over the
lower portion. Rotate the 2 Allen head screws counter-
clockwise until the cover is secured to the mounting plate
and locked in position.
NOTE: See Table 3 for thermistor resistance vs temperature
values.
Table 3 — Thermistor Resistance vs Temperature
Values for Space Temperature Sensor,
Supply Air Temperature Sensor, and
Outdoor Air Temperature Sensor
Wiring the Space Temperature Sensor
— To wire the sensor,
perform the following (see Fig. 3-6):
1. Identify which cable is for the sensor wiring.
2. Strip back the jacket from the cables for at least 3 inches.
Strip
1
/
4
-in. of insulation from each conductor. Cut the
shield and drain wire from the sensor end of the cable.
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
–40 –40 335,651
–35 –31 242,195
–30 –22 176,683
–25 –13 130,243
–20 –4 96,974
–15 5 72,895
–10 14 55,298
–5 23 42,315
0 32 32,651
5 41 25,395
10 50 19,903
15 59 15,714
20 68 12,494
25 77 10,000
30 86 8,056
35 95 6,530
40 104 5,325
45 113 4,367
50 122 3,601
55 131 2,985
60 140 2,487
65 149 2,082
70 158 1,752
2
3
45
61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
Fig. 3 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)