OUTDOOR AIR TEMPERATURE SENSOR (Fig. 16-19) —
The OAT sensor must be located properly. For outdoor loca-
tions use sensor 33ZCSENOAT. For duct mounting in the
fresh air intake, use sensor 33ZCSENPAT. The sensor must be
installed immediately upstream from outdoor-air damper
where it will accurately sense the temperature of the outdoor
air entering the mixing box. See Fig. 16 and 17. For applica-
tions without economizer, the sensor may be located in the out-
door air duct near the outdoor-air intake (Fig. 17) or on the
exterior of the building (Fig. 16). The thermistor has a range of
–40 to 245 F and a resistance of 10,000 ohms at 77 F.
Do not mount the sensor in direct sunlight. Inaccurate read-
ings may result. Do not mount the sensor near the exhaust from
air-handling units or compressors, near leakage drafts of indoor
air, or near shrubbery or trees, or under direct water runoff.
If the sensor is installed outdoors, perform the following in-
structions. Install the
1
/
2
-in. conduit connector into the rear
opening. Tighten the conduit connector securely to prevent
water leakage into the assembly. Mount the assembly onto the
1
/
2
-in. conduit and secure by tightening the conduit nut. After
the sensor wiring is completed, secure the gasket and cover in
place using the screws provided with the cover. See Fig. 18.
If the sensor is to be mounted in the outdoor air duct, use the
33ZCSENPAT sensor which has a 2 x 4-in. by 1
1
/
2
-in. deep
electrical box. Remove the cover and enter the knockout from
the rear of the box. Install the sensor through the opening so
that the sensor leads are inside the electrical box. Secure the
sensor to the electrical box using a field-supplied
1
/
2
-in. con-
duit nut. Drill a
1
/
2
-in. hole in the outdoor-air duct about a foot
upstream of the outdoor-air damper. Apply a
1
/
4
-in. bead of sil-
icone type sealer around the opening and install the sensor
through the hole. Secure the electrical box to the duct using 2
field-supplied, no. 10 sheet metal screws. See Fig. 19.
FACTORY-INSTALLED CONTROLLER — The Premier-
Link™ controller is available as a factory-installed option on
some units. Additional terminal boards are provided for wiring.
Sensors and input devices are wired to terminal boards instead
of directly to the Premierlink controller. See Fig. 20.
Connect Discrete Inputs — If used, wire the dry con-
tact switches, compressor safety switch, and supply fan status
switch to the PremierLink controller. See Fig. 21 for wiring.
Fig. 16 — Outdoor Air Temperature Sensor
Installation — Located on Building Wall
(P/N 33ZCSENOAT)
RETURN
AIR
OAT
OUTDOOR
AIR
ROOF TOP
UNIT
Fig. 17 — OAT Sensor Location
in Outside Air Duct (P/N 33ZCSENPAT)